Télécharger Imprimer la page

S+S Regeltechnik PREMASREG 7111 Notice D'instruction page 10

Masquer les pouces Voir aussi pour PREMASREG 7111:

Publicité

Les langues disponibles

Les langues disponibles

G
®
PREMASREG
7111
Quality product for HVAC sector, accuracy ± 1.5 %
The electronic PREMASREG
®
one continuous output, and a display for setting the switchpoint and to display the ACTUAL pressure (eight devices in one, plus differential pressure
switch ⁄ differential pressure monitor, continuous pressure sensor in a single device). The pressure sensor is used for above-atmospheric,
below-atmospheric, or differential pressure measurement in clean air with limit value switching. The piezo-resistive measuring element guarantees a
high degree of reliability and accuracy. Applications of these pressure sensors are in clean room, medical and filter technology, in ventilation and air
conditioning ducts, in spray booths, in large-scale catering facilities, for monitoring filters, for level measurement or for triggering frequency
converters. Media measured with these pressure transducers are air (non-precipitating), or other gaseous non-aggressive, non-combustible media.
The pressure sensor has a manual zero point pushbutton and an offset potentiometer for final value and switchpoint correction. Fine adjustment by
the user is possible at any time. The delivery includes the connection set ASD-06 (2 m connection hose, two pressure connection nipples, screws).
TECHNICAL DATA
Voltage supply:
Power consumption:
Measuring ranges:
Output signal:
Electrical connection:
Media temperature:
Pressure connection:
Type of pressure:
Medium:
Accuracy:
Sum of
Linearity+hysteresis:
Temp. drift values:
Zero point offset:
Above- ⁄ below-atmospheric
pressure:
Signal filtering:
Setting increment Δp:
Switching hysteresis:
Enclosure:
Dimensions:
Electrical connection:
Cable gland:
Air humidity:
Protection class:
Protection type:
Standards:
Equipment:
ACCESSORIES:
7111 pressure sensors and switches are equipped with eight switchable measuring ranges, one switching output and
24 V AC ⁄ DC (± 20 %)
< 1 VA ⁄ 24 V DC, < 2.2 VA ⁄ 24 V AC
multi-range switching
with 8 switchable measuring ranges (see table)
0 -10 V
1 changeover contact (24 V ⁄ 1 A)
3-wire connection (U)
0...+50 °C
4 ⁄ 6 x 11 mm (hoses Ø = 4 ⁄ 6 mm),
metal pressure connection nozzles
differential pressure
clean air and non-aggressive, non-combustible gases
± 1.5 % of final value (at +20°C)
< ± 1 % of final value
± 0.1 % ⁄ °C
< ± 0.7 % of final value
max. ± 100 hPa
switchable 1 s ⁄ 10 s
1 % of pressure range (100 Pa => 1 Pa; 5000 Pa => 50 Pa)
± 1 % of pressure range (100 Pa => ± 1 Pa; 5000 Pa => ± 50 Pa)
plastic, material polyamide, 30 % glass-globe reinforced,
with quick-locking screws (slotted ⁄ Phillips head - combination),
colour traffic white (similar to RAL 9016), enclosure cover for display is transparent!
126 x 90 x 50 mm (Tyr 2)
0.14 - 1.5 mm², via plug-in screw terminal
M 16 x 1.5; including strain relief
< 95 % r. H., non-precipitating air
III (according to EN 60 730)
IP 65 (according to EN 60 529)
CE conformity according to EMC Directive 2004 ⁄ 108 ⁄ EC,
according to EN 61326-1, according to EN 61326-2-3
three-line display with illumination, cutout approx. 70 x 40 mm (W x H),
for displaying ACTUAL pressure and ⁄ or SETPOINT pressure
and for adjusting the automatic zero point calibration
incl. connection set ASD - 06 (nipple straight)
(included in the scope of delivery)
Connection nipple ASD - 07 (at 90° angle)
Pressure outlet DAL -1 for ceiling- or in-wall installation (e.g. in clean rooms)
10
Rev. 2016 - V23 GB

Publicité

loading