ATEX:
Certified to EN60079-0, EN60079-1 & EN60079-31
Ex d unit (ATEX certification No. Bas03ATEX0463)
Ex d IIC T6 Gb (Tamb. -55°C to +55°C)
T5 Gb (Tamb. -55°C to +70°C)
T4 Gb (Tamb. -55°C to +85°C)
Ex tb IIIC T85°C Db (Tamb. -55°C to +55°C) IP66/67
T100°C Db (Tamb. -55°C to +70°C)
T135°C Db (Tamb. -55°C to +85°C)
Note: For details of specific ratings with components (resistors, diodes, modules etc.) fitted, see the ATEX
certificate or certification label fitted to the unit.
The ATEX certificate and product label carry the ATEX group and category marking:
II 2 GD
Where:
Signifies compliance with ATEX
II
Signifies suitability for use in surface industries
2
Signifies suitability for use in a zone 1 area
G
Signifies suitability for use in the presence of gases
D
Signifies suitability for use in the presence of dust
© Cooper MEDC 2013
07/13