Télécharger Imprimer la page

MEDC SM87 Manuel Technique page 3

La boîte de jonction

Publicité

Les langues disponibles

Les langues disponibles

1.0 INTRODUCTION
The SM87 Junction Box has been designed for use in flammable atmospheres and harsh environmental
conditions. The unit is available in marine grade alloy or stainless steel
2.0 GENERAL SAFETY MESSAGES AND WARNINGS
All instructions and safety messages in this manual must be followed to allow safe installation of the device. The
device must only be installed and maintained by correctly trained site personnel/installers.
i.
To reduce the risk of ignition of hazardous atmospheres and shock, do not apply power to the device
until installation has been completed and the device is fully sealed and secured.
ii.
To reduce the risk of ignition of hazardous atmospheres and shock, keep device tightly closed when the
circuit is energised.
iii.
Before removing the cover for installation or maintenance, ensure that the power to the device is
isolated.
iv.
Following installation, test the device to ensure correct operation.
v.
Following installation ensure a copy of this manual is made available to all operating personnel
vi.
When installing the device, requirements for selection, installation and operation should be referred to
e.g. IEE Wiring Regulations and the 'National Electrical Code' in North America. Additional national
and/or local requirements may also apply.
vii.
Cable termination should be in accordance with specification applying to the required application.
MEDC recommends that all cables and cores should be correctly identified. Please refer to the wiring
diagram in this manual (or separate diagram provided with the unit).
viii.
Ensure that only the correct listed or certified cable glands are used and that the assembly is shrouded
and correctly earthed.
ix.
Ensure that only the correct listed or certified stopping plugs are used to blank off unused gland entry
points and that the NEMA/IP rating of the unit is maintained.
x.
MEDC recommend the use of a sealing compound such as HYLOMAR PL32 on the threads of all glands
and stopping plugs in order to maintain the IP rating of the unit.
xi.
The internal earth terminal, where fitted, must be used for the equipment grounding and the external
terminal, if available, is for a supplementary bonding connection where local codes or authorities
permit or require such a connection.
xii.
When installing the device, MEDC recommends the use of stainless steel fasteners. Ensure that all nuts,
bolts and fixings are secure.
3.0 INSTALLATION
General
The junction box is mounted via 4 off
The fixing holes have been designed to accept M8 screws or bolts.
Removing/replacing the Cover
Unscrew and remove the 4 off M6 screws (5mm A/F hexagon key required) holding the cover to the base of the
enclosure. Twist the cover gently clockwise and anti-clockwise whilst pulling away from the base. Lift the cover
clear of the base. The screws are not captive and should be kept in a safe place during cable termination
Once cable termination has been completed, the cover can be replaced and secured to the enclosure. Ensure that
any cover seal is correctly seated. Once the cover screws have been fully tightened, ensure the gap between the
cover and enclosure is 0.15mm max.
© Cooper MEDC 2013
9mm fixing holes in feet on the base of the unit.
07/13

Publicité

loading