Tecla sensora con receptor vía radio
Run­on time
Behaviour after the end of the
disabling function
Behaviour on voltage return
Brightness on voltage return
Switch­off warning
Priority, lock­out protection
Priority, restraint
32582703
J:0082582703
0 s ... 24 h
Basic setting: 0 s
On
Off
no change
Last value
Basic setting: No change
On
Off
Last value
Configured brightness
Basic setting: Off
0...100 %
Basic setting: 100 %
On, Off
Basic setting: Off
0...4
Basic setting: 1
0...4
Basic setting: 2
7/10
As soon as a run­on time has
been entered, the actuator will
no longer remain on perma­
nently, but only for the length
of the run­on time. The run­on
time is restarted if actuation is
repeated. This parameter is di­
rectly connected to the "Ma­
nual switch­off of run­on time"
parameter.
Behaviour of the output when
a block is removed.
Defines the behaviour of the
output after voltage return.
Brightness value, set by the
output after voltage return
(mains voltage). The parame­
ter "Behaviour after voltage re­
turn" must be set to "Configu­
red brightness".
Note: If the value is above the
set maximum brightness or
below the minimum bright­
ness, then the system will
switch to the appropriate limit
value.
If the switch­off warning is ac­
tive, then, during switch­off,
the systems dims to minimum
brightness within 30 seconds
and only then switches off. If
the parameter "Dim down
ramp" is configured as longer
than 30 s, then the length of
the dim down ramp is applied.
If, during the dim down opera­
tion, another command is gi­
ven, e.g. switch on or scene
recall, then the switch­off war­
ning stops and the command
is executed. A switch­off com­
mand restarts the time for the
switch­off warning.
Specifies the priority for recal­
ling and removing a scene of
type Lock­out protection for
the channel.
Note: 1 is the highest priority
and 4 the lowest. 0 means no
priority.
Specifies the priority for recal­
ling and removing a scene of
type Forced position for the
channel.
14.03.2014