Circulation Unit - Riello BAG2 MIX CLIMA Mode D'emploi

Masquer les pouces Voir aussi pour BAG2 MIX CLIMA:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

HYDRAULIC CIRCUIT
HYDRAULIC CIRCUIT
HYDRAULIC CIRCUIT
HYDRAULIC CIRCUIT
HYDRAULIC CIRCUIT
E -
Inlet (3/4")
U –
Outlet (3/4")
MD –
Delivery, direct system (3/4")
Mmix – Delivery, mixed system (1")
Rmix – Return, mixed system (1")
RD –
Return, direct system (3/4")
The maximum length of plumbing connec-
tions between the boiler and the
unit must not exceed 15 m.
CLIMA
C C C C C IRCULATION UNIT
IRCULATION UNIT
IRCULATION UNIT
IRCULATION UNIT
IRCULATION UNIT
2
The BAG
MIX CLIMA is fitted with two circulation units, the
performance data to be used to size the system, is shown
in the graph.
When starting up for the first time, and at least once a
year, it is advisable to check the pump units shaft
rotate.
This is necessary because, especially after lengthy
CIRCULATOR RESIDUAL HEAD
HIGH TEMPERATURE SYSTEM
5,5
5,0
4,5
4,0
3,5
3,0
2,5
2,0
1,5
1,0
0,5
0,0
0
200
400
600
1 - first speed
2 - second speed
3 - third speed
16
GENERAL
2
BAG
2
1
800
1000
1200
1400
1600
1800
Capacity (l/h)
MIX
MD
periods of inactivity, deposits and/or residue may stop
it rotating freely.
Do not run the circulation units without water.
Where present in low system flo regulator devices
(thermostatic electrical or motorized zone valves) it is
better to inster a by pass on the low temperature
system collector.
CIRCULATOR RESIDUAL HEAD
LOW TEMPERATURE SYSTEM
7,5
7,0
6,5
6,0
5,5
5,0
4,5
4,0
3,5
3
3,0
2,5
2,0
1,5
1,0
0,5
0,0
0
200
400
2000
1 (
) first speed with close mix valve
1 (
) first speed with open mix valve
2 (
) second speed with close mix valve
2 (
) second speed with open mix valve
3 (
) third speed with close mix valve
3 (
) third speed with open mix valve
E
U
Mmix
Rmix RD
1
600
800
1000
1200
1400
Capacity (l/h)
3
2
1600
1800
2000

Publicité

Table des Matières
loading

Table des Matières