Télécharger Imprimer la page

Ariston Chaffoteaux 3024151 Installation Et Mode D'emploi page 41

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 48
start-up
disease function:
0 OFF
1 ON
Turn the knob and set value 1 to activate
the anti-Legionnaire's disease function.
Press the OK button.
The display will visualise the selected set-
ting.
Press OK button to return to the previous
visualisation.
Turn the knob and select:
- 3 2 1 Hydraulics diagram
Turn the knob to verify or set the refer-
ence hydraulics diagram according to
the effected installation:
0 Not defi ned
1 Basic single-coil
2 Basic double-coil
3 Solar-electric
4 Heating integration
Press the OK button.
The display will visualise the selected setting.
Press OK button to return to the previous
visualisation.
Turn the knob and select:
- 3 2 2 Heating element operation
Press the OK button.
Turn the knob and set value 1 if the user
desires that the heating integration - via
the heating element - occurs according to
a time schedule.
Press the OK button.
The display will visualise the selected setting.
Press OK button to return to the previous
visualisation.
Turn the knob and select:
- 3 2 3 DeltaT collector
for pump activation
Press the OK button.
Turn the knob and set the temperature dif-
ference between the collector and storage
tank that determines the pump's activa-
tion.
NOTE: INCREASE THE VALUE IF THE
PUMP TURNS ON/OFF FREQUENTLY.
Press the OK button.
The display will visualise the selected setting.
Press OK button to return to the previous
visualisation.
Turn the knob and select:
- 3 2 4 DeltaT collector
for pump stoppage
Press the OK button.
Turn the knob and set the temperature dif-
ference between the collector and storage
tank that determines the pump's stoppage.
NOTE: DECREASE THE VALUE IF THE
PUMP TURNS ON/OFF FREQUENTLY.
Press the OK button.
The display will visualise the selected set-
ting.
Press OK button to return to the previous
visualisation.
Turn the knob and select:
- 3 2 7 Recooling Function
Press the OK button.
Turn the knob and set value 1 to activate
the Recooling function.
NOTE: this function delays overheating of
the collector by cooling the indirect cylin-
der during the night.
Press the OK button.
The display will visualise the selected setting.
Press OK button to return to the previous
visualisation.
Turn the knob and select:
- 3 2 9 T Collector Anti-Freeze
Press the OK button.
Turn the knob and set value 0 for enhancing
the anti-freeze protection for the collector.
Set -20 if high percentages of glycol are
used.
Press the OK button.
The display will visualise the selected set-
ting.
Press OK button to return to the previous
visualisation.
Turn the knob and select:
- 3 6 0 Solar circuit fl ow rate
The display will visualise the value of the
fl ow rate in the solar circuit.
GB
41

Publicité

loading

Ce manuel est également adapté pour:

Chaffoteaux 3024159