TAS 03
Parameter
Mode of action (DIN EN
14597)
Operating temperature range
Operating temperature
At capillary tube and probe
Response temperature
(DIN EN 14597)
Ambient temperature valve
Material
Housing
Spring / pressure bolt
Functional parts
Pocket
Probe system
Diagram 1: Maximum flow/inlet pressure
– English –
Value
Type Th 2KP
5 to 115 °C
Short-term max. 125 °C
99 °C (area opening point
between 92 °C and 99 °C)
Max. 80 °C
Brass
Stainless steel
Plastic
Brass, nickel-plated
Copper with silicone oil filling
Technical specifications