Setting Up the Transducer
1. Turn the transducer power supply on. The instrument will go through a
preprogrammed power-up sequence. The internal display will sequence
through the current settings: Calibration date "CALdAtE", "=", month
and year "03.1995"(March 1995), measurement units "mEtErS"(m/s)
or "FEET"(ft/min), "=", selected output type and range "0-5V" and the
time constant "tc = 1.00" in seconds. The display will then show
velocity readings.
2. Push the SET button to enter setup mode. When setup mode is
entered, the transducer voltage/current output will drop below zero.
3. Use the t and s buttons to select the desired setting.
4. Use the SET button to advance to the next setup message.
Note:
The output signal is disabled during the 15 second warm-up period
and when the transducer is in setup mode.
Setup Message
SELECt UnitS
SELECt FULL
SCALE
SELECt OUtPUt
SELECt tc
AdJUSt ZErO
AdJUSt SPAn
FEEt (ft/min) or mEtErS (m/s)
Select full scale of the velocity range
Select Output Type: 0-5V, 0-10V, 1-5V, 2-10V, 4-
20mA, 0-20mA
Select Time Constant: 0.05 to 10 seconds (see page
12)
Adjusts voltage/current output signal at zero velocity
(see page 14)
Adjusts the voltage/current output by ±15% (see page
13)
9
Available Settings