CAUTION: Use only the No. P-0716-UV
smoke-producing solution (obtained from
the manufacturer) in the LeakMaster. Using
solutions not recommended by the manufacturer
can damage the unit and cause injury to the
operator.
Checking the Smoke Solution Level
Check the smoke-producing solution in the tester
regularly, and top off the solution to the FULL mark.
(Order No. P-0716-UV.)
1. Remove the dipstick located on the back of the
tester and verify the solution level. Add solution,
if needed.
2. Install the dipstick, and then remove it again to
verify the solution level reads at the FULL mark
on the dipstick. Install the dipstick.
Replacing the Smoke Solution
We recommend changing the smoke-producing
solution in the tester at least once a year, regardless
of how often the tester has been used.
1. Remove the dipstick located on the back of the
tester.
2. Insert a suction tool into the dipstick tube,
and suction all the solution out of the smoke
chamber.
IMPORTANT: Do not damage the water
separator on the back of the tester.
3. Refull the smoke chamber by emptying 16 ozs. of
UltraTraceUV
smoke-producing solution (No.
®
P-0716-UV) into the smoke chamber through the
dipstick tube.
4. Install the dipstick, and then remove it again to
verify the solution level, which should read at the
FULL mark on the dipstick. Note: Do not overfill.
Install the dipstick.
5. Record your name and the date in the Fluid Change
Record in this manual.
6. Dispose of the waste smoke solution according to
local, state, and federal (OSHA) regulations.

Maintenance

LOW
FULL
Dipstick
17