Installation and Operating Instructions
m
m
DANGER
DANGER
CHAPTER 3
TECH. DATA
WIRING DIAGRAM
Damper Servo Motor STM .. 24 V 2P
2.1
Electrical connection / Commissioning
m The safety instructions specified in section 1.2 must be observed!
– The electrical connection and initial commissioning must only be carried out
by qualified electricians according to the information in the attached wiring
diagram.
– The relevant standards, safety regulations (e.g. DIN VDE 0100), as well as
the technical connection conditions of energy suppliers are to be adhered
to!
– An all-pole mains switch/isolator, with at least a 3 mm contact opening (VDE
0700 T1 7.12.2 / EN 60335-1) is mandatory!
– Network configuration, voltage and frequency must be consistent with the
rating plate information.
3.0 Technical data
Nominal voltage
Power consumption
Peak inrush current
Torque
Angle of rotation
Running time Motor
Running time Spring return
Potential-free signal contacts
Environmental temperatures
Storage temperature
Protection category
Protection class
Dim. W x H x D (mm)
Weight
Assembly circular
Assembly square
Connection servo motor
Connection signal contacts
Wiring diagram
STM 10 24 V 2P
AC 24 V, 50/60 Hz / DC 24 V
8.5 VA/24 V AC (355 mA)
8.2 A/5 ms
10 Nm
0 to 95°
approx. 75 s
approx. 20 s
2x changeover contact, 250 V AC / 1 mA to
3 A (0.5 A inductive)
-30 to +50 °C
-40 to +80 °C
IP54
III
98 x 214 x 93
2.0 kg
10-25 mm (diameter)
10-18 mm (edge length)
Cable length 1m, 2 x 0.75 mm²
Cable length 1m, 6 x 0.75 mm²
SS-1090
4
EN
STM 20 24 V 2P
7.5 VA/24 V AC (312 mA)
8.2 A/5 ms
20 Nm
2.3 kg