Dimensions and Wiring
3⁄4"
A
C
E
D
Dimensions and Wiring
D
A1 A2
D
F
C
115/230 Volt Single Phase Fans
Wiring schematic for 4 lead motors, single phase
Notes:
1. All leads are color coded
as well as identified with an
Alpha/Alpha or Alpha/
Numeric code (i.e.TK or
Z2).This code may be
shown as a band on the
wire or on a schematic on
the motor hub. Colors
should be verified against code band. If code band and color do not
correspond to schematics above, wire according to the code on the band.
2. Color of capacitor leads may be reversed. Fan operation will not be
affected.
230 Volt Three Phase Fan
Notes:
1. Contactor should be used.
Control coil should be
wired in series with motor
Motor
thermal contacts (TK
Leads
leads) as shown in diagram
to provide thermal motor
protection.
2. All leads are color coded
as well as identified with a band containing an Alpha/Alpha or
Alpha/Numeric code (i.e.TK or Z2). Colors should be verified against code
band. If code band and color do not correspond to schematics above, wire
according to the code on the band.
(Models FKD 8XL, 10, 10XL, 12S, 12, 14S)
Dimensional Data
Model
A
8
FKD 8XL
10
FKD 10
10
FKD 10XL
12
FKD 12S
12
FKD 12
All dimensions in inches.
† FKD 14s overall length is 8"
(Models FKD 12XL, 14, 14XL, 16, 16XL, 18, 18XL, 20)
H
Dimensional Data
Model
FKD12XL 12
FKD14
A
B
B1
FKD14XL 14
FKD16
FKD16XL 16
FKD18
G
FKD18XL 18
All dimensions in inches.
Green/Yellow (
)
(Ground)
Motor
Brown-TK
L (Black)
Leads
Blue-U2
N (White)
Black-Z1
Capacitor
Green/Yellow (
)
(Ground)
Orange-W2
Brown-U1
Line 1
Red-U2
Blue-V1
Line 2
Grey-V2
Line 3
Black-W1
White-TK
White-TK
5
C
D
E
Weight
12¹⁄₂ 15¹⁄₂
7
19 lbs.
12¹⁄₂ 12¹⁄₂
7
21 lbs.
14
15
8
15 lbs.
12¹⁄₂
10
7
22 lbs.
14
12¹⁄₂
8
16 lbs.
A
A1 A2
B
12 17⁷⁄₈ 20¹⁄₄ 18⁷⁄₈ ⁷⁄₈
-
14 19³⁄₄ 22¹⁄₈ 20¹⁄₄ 1¹⁄₂ 1⁵⁄₈
14
-
14 19³⁄₄ 22¹⁄₈ 20¹⁄₄ 1¹⁄₂ 1⁵⁄₈
-
19³⁄₄ 22¹⁄₈ 18¹⁄₄ 1¹⁄₂ 1⁵⁄₈
16
16
-
16 22¹⁄₈ 24³⁄₈ 23¹⁄₄ 1¹⁄₄ 1⁵⁄₈
-
22¹⁄₈ 24³⁄₈ 21³⁄₄ 1¹⁄₄ 1⁵⁄₈
18
18
-
18 28¹⁄₈ 30³⁄₈ 30⁵⁄₈ 2
-
460 Volt Three Phase Fan
Important note: For 460 volt operation, Orange (W2), Red (U2) and
Notes:
Supply
1. Contactor should be used.
Voltage
Control coil should be wired
in series with motor thermal
contacts (TK leads) as shown
in diagram to provide thermal
motor protection.
2. All leads are color coded as well as identified with a band
containing an Alpha/Alpha or Alpha/Numeric code (i.e.TK or Z2). Colors
should be verified against code band. If code band and color do not
correspond to schematics above, wire according to the code on the band.
Contactor for 3-Phase Fans, 208-230/460v
Supply
Voltage
Control Power
for Contactor
115 Volt Single Phase Fans
Green/Yellow
Blue
Motor
Leads
Black
Brown
Capacitor
B1
C
D
E
F
1⁵⁄₈
4
4 11¹⁄₈ ³⁄₈ 45 lbs.
4 11¹⁄₈ ³⁄₈ 55 lbs.
4
⁷⁄₈
⁷⁄₈
1³⁄₄
⁷⁄₈ 12¹⁄₂ ¹⁄₂ 95 lbs.
Grey (V2) wires must be spliced together.
Green/Yellow (
)
Orange-
W2
Brown-U1
Motor
Red-
U2
Blue-V1
Leads
Grey-
V2
Black-W1
White-TK
White-TK
Incoming
3-Phase Supply 208/230/460
C1
AC Contactor
T1
T2
T3
L1
L2
L3
C2
TK
TK
L1
L2
L3
L3
Motor Leads
(Ground)
Supply
N (White)
Voltage
L (Black)
G
H Weight
7³⁄₄
³⁄₈ 45 lbs.
9¹⁄₂
³⁄₈ 55 lbs.
8¹⁄₂
¹⁄₂ 85 lbs.
¹⁄₂ 85 lbs.
7
(Ground)
Line 1
Supply
Line 2
Voltage
Line 3
Ground