Symboles de sortie
xDewPoint
xGasInletValve
xGasOutletValve
xCoolingWaterValve
xDryer1Valve
xDryer2Valve
uiErrorCodeAlarmTrigger
uiErrorCodeLastWarning
uiInterfaceVersionNr
uiNominalOzoneCapacity
uiControlRangePercentage
rTemperatureCoolingWater
rGasFlowRate
rGasPressure
udiOperatingHours
udiOperatingHoursWithOzone
iNextMaintenace
wReserved1
wReserved2
wReserved3
wReserved4
wReserved5
Liste des paramètres du bus de terrain pour l'installation OZONFILT OZVb
Type
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
UINT
UINT
UINT
UINT
UINT
REAL
REAL
REAL
UDINT
UDINT
INT
WORD
WORD
WORD
WORD
WORD
OZONFILT as
OZONFILT as
Profibus Slave
Modbus RTU
Device as Pro‐
Slave as
fNet Device
Modbus TCP
Server
32 word
Register-
output_0
Addresse
(0x80,0x5F)
(0..55)
WORD6.10
06.10
WORD6.11
06.11
WORD6.12
06.12
WORD6.13
06.13
WORD6.14
06.14
WORD6.15
06.15
WORD8
08
WORD9
09
WORD11
11
WORD12
12
WORD13
13
WORD14 ...
14...15
WORD15
WORD17 ...
17...18
WORD18
WORD19 ...
19...20
WORD20
WORD21 ...
21...22
WORD22
WORD23 ...
23...24
WORD24
WORD25 ...
25...26
WORD26
WORD27
27
WORD28
28
WORD29
29
WORD30
30
WORD31
31
Unité
"TRUE" or
"FALSE"
"TRUE" or
"FALSE"
"TRUE" or
"FALSE"
"TRUE" or
"FALSE"
"TRUE" or
"FALSE"
"TRUE" or
"FALSE"
unitless quantity
unitless quantity
unitless quantity
g/h
%
°C
l/h
bar
h
h
days
N/A
N/A
N/A
N/A
N/A
21