2. Turn off the 3-phase power. Swap any two leads: L1 and L2; L2 and L3; L3 and L1. You have a 50-50
chance of connecting L1, L2 and L3 up correctly the first time. Turn on the 3-phase power.
®
3. If the MotorSaver
the average of the voltages. If the average voltage is 10% above (high voltage protection standard on
Model 250 only) or 10% below the voltage adjust setpoint, the MotorSaver
saving your motor from abnormal power conditions.
4. If the average of the three line voltages is within ±10%, calculate the voltage unbalance using the
NEMA method shown below:
% voltage unbalance = (max. deviation / average of the three voltages) x 100
EXAMPLE: Find the largest deviation from the average voltage and divide it by the average for the
NEMA unbalance.
L1 - L2 = 460VAC, L2 - L3 = 466 VAC, L3 - L1 = 490 VAC
Average = (460 + 466 + 490)/3 = 472
490 is the largest deviation from the average voltage.
Max. deviation = 490 - 472 = 18
% voltage unbalance = (18/472) x 100 = 3.8%
If the percent voltage unbalance is greater than 4.5%, MotorSaver
motor from abnormal power conditions.
5. If the percent voltage unbalance is less than 4.5%, contact SymCom at 1-800-843-8848 OR
1-605-348-5580 and we will be happy to help you.
LINE VOLTAGE ADJUST
208/416
200/400
190/380
(VAC)
FRONT
LINE VOLTAGE
L1
ADJUST
208
220
190-480 VAC, 3Ø, 50/60 HZ
416
440
200
230
400
460
190
240
380
480
(VAC)
MODEL 102
P/N- MS102 - A
GEN. PURPOSE RATING
10 A at 240 VAC
PILOT DUTY RATING
480 VA at 240 VAC
4.030" (102.36)
4.500" (114.30)
5.250" (133.35)
Seller warrants to the buyer that products furnished will be free from defects in material and workmanship, exclusive
of corrosion, for a period of five years from the date of shipment from its factory, provided said products have been
installed, maintained and operated in conformance with any applicable specifications and recommendations of the
Seller. The sellers liability under this warranty shall be limited to the replacement within the aforesaid time of any defec-
tive work or material limited at the Seller's factory and shall not be liable for any labor or other repair costs made out-
side the Seller's factory without the written consent of the Seller. The Seller shall be liable for no other damages or
losses. The warranty described in this paragraph shall be IN LIEU OF ANY OTHER WARRANTY EXPRESSED OR
IMPLIED INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE.
still seems to be malfunctioning, measure the three line-to-line voltages. Calculate
DIMENSIONS FOR MODEL 201
220/440
230/460
240/480
RUN LIGHT
TOP
DIMENSIONS FOR MODELS 102, 250, 350
RESTART
L2
L3
DELAY
70
150
2
220
MAN
300
(SECONDS)
RUN
LIGHT
IND. CONT. EQ
IND. CONT. EQ
U L
U L
C
®
®
LISTED
LISTED
1.75
(44.545)
2.375
(60.331)
BOTTOM
2.900"
(73.66)
.375"
(9.53)
WARRANTY
®
is functioning properly,
®
is functioning properly, saving your
3.15
(80.010)
.5
(12.700)
SIDE
SIDE
0.150" (3.81)
2.913"
(73.99)
2.163"
(54.94)

Publicité

Table des Matières
loading

Table des Matières