Layout Of Electrical Terminals - Toshiba Carrier TCB-CC163TLE Manuel D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 20

Layout of electrical terminals

Clamp for electrical wiring
Earth for
power
N
wiring
L
B3 B2 B1 A3 A2 A1
How to connect electrical wiring
1) Basic wiring
N:
Power supply (
L:
Power supply wire specification: Cable 3-core, in
conformance with Design 60245 IEC 57.
Fix the wires with code clamp.
Earth line
Power supply wire
U1/U3:
Central control wiring. (Low voltage)
U2/U4:
C3:
Auxiliary
C4:
Ground for Central control wiring
2) Terminals for remote monitoring
A1:
Input for turning on air conditioners concurrently.
A2:
Input for turning off air conditioners concurrently.
A3:
Common input for turning air conditioners on or off.
B1:
On operation state indicator output.
B2:
Alarm indicator output.
B3:
Common indicator output.
Wire connection
Power supply wire specification: Cable 3-core 1 mm
OI-744-07EG
Connector (CN02)
for weekly timer
(optional)
CN02
U1/U3
P.C. board
U2/U4
C3
C4
50 Hz/60 Hz, 220 – 240 V)
2
, in conformance with Design 60245 IEC 57.
CN02
U1/U3
N
U2/U4
L
C3
B3 B2 B1 A3 A2 A1
C4
Fig. 3
Rear plate
EG
7

Publicité

Table des Matières
loading

Table des Matières