Boarding materials
Wall types
Drywall
F30, F60 and F90
Drywall
F120
F30
-
F120
Wood panel,
wood frame
construction wall
F30-B
Wood panel,
wood frame
construction wall
F60-B
F30-B
-
F60-B
Shaft wall
I30, I60 and I90
F30
-
F90
Labelling
1
Wood or framework stand
Double panelling on both sides with 12.5 mm thick non-
2
combustible mineral gypsum- or cement-bound
Internal insulation of at least 40 mm thick
mineral wool (glass or rock wool) with a gross density of
3
at least 14 kg/m³, melting point > 1.000°C is not
1
Double boarding on both sides with 15 mm thick
2
plasterboard fire protection panels (GKF)
Internal insulation of at least 40 mm thick
3
non-combustible mineral wool with a melting point >
1
Wooden framework 40x60 mm
Double panelling on both sides with ≥15 mm thick OSB-,
2
plywood or MDF boards (bulk density ≥ 550 kg/m³)
Double layer panelling on both sides with ≥ 9.5 mm thick
3
non-combustible cement- or gypsum-bond building board
Internal insulation of at least 40 mm thick
mineral wool (glass or rock wool) with a bulk density
of at least 14 kg/m³, melting point > 1.000°C is
4
not absolutely necessary, or normally flammable
wood wool or wood fibre insulation with a bulk density
1
Wood framework 80 mm
Double panelling on both sides with ≥15 mm thick OSB-,
2
plywood or MDF boards (bulk density ≥ 550 kg/m³)
Double layer panelling on both sides with ≥ 12.5 mm thick
non-combustible 87 / 5000
3
Übersetzungsergebnisse mineral gypsum or cement-bonded
building boards or calcium silicate boards (GRP)
Internal insulation of at least 60 mm thick
mineral wool (glass or rock wool) with a bulk density
of at least 14 kg/m³, melting point > 1.000°C is
4
not absolutely necessary, or normally flammable
wood wool or wood fibre insulation with a bulk density
1
Double panelling on both sides with 20 mm (for use with
the one-gang box) 25 mm (when using accessory
2
junction box) thick non-combustible mineral
gypsum or cement-bound building boards
I60 - 40 mm / 100 kg/m³; 60 mm
3
/ 50 kg/m³; 80 mm / 30 kg/m³
I90 - 40 mm / 100 kg/m³ Termarock 100
Description
building panels
mandatory
Steel framework
1,000°C
(GKB)
≥ 50 kg/m³
≥ 50 kg/m³
Steel framework
I30 - no insulation