Télécharger Imprimer la page

Raychem Gardian W51 Mode D'emploi page 4

Publicité

4
Figure 3 Insulation
4. Install thermal insulation.
• A reliable Gardian system depends on properly installed and dry,
weatherproofed thermal insulation.
• Ensure that at least 1/2" of preformed foam or equivalent thermal
insulation is used and that all piping, including valves, joints, and wall
penetrations, has been fully insulated as shown in Figure 3.
• For protection to -20°F (-29°C), use 1" thick insulation.
• Install the insulation on the piping as soon as possible to minimize the
potential for mechanical damage after installation.
• Be sure the Gardian W51 label is visible on the outside of the thermal
insulation.
5. Finishing the installation.
• To prevent damage to the heating cable or cord, secure the
power cord (cold lead) with a plastic cable tie, glass cloth tape,
or duct tape as shown in Figure 4.
• Two labels indicating the presence of electric pipe heating cable are
included with the heating cable. Attach the two "Electric Traced" labels
on the outer surface of the pipe insulation at suitable internals to
indicate the presence of Gardian electric heating cable.
Cable testing and maintenance
Using a 2500-Vdc megohmmeter, check the
WARNING! Fire and shock hazard.
insulation resistance between both of the
Damaged heating cable can cause electrical
rectangular (power) prongs on the plug and
shock, arcing, and fire. Do not attempt to
the round (ground) prong after installing the
repair or energize damaged heating cable.
heating cable. Minimum reading should be
Remove it at once and replace with a
1000 megohms.
new length.
Record the original values for each circuit, and
compare subsequent readings taken during
regular maintenance schedules to the original
values.
If the readings fall below 1000 megohms,
replace the Gardian W51 cable with a new
unit. Do not attempt to repair the unit.
Figure 4 Strain relief
Strain relief
Cord label
Pipe label
Note:
Pipes must be fully insulated.
6. Starting the system.
• Tyco Thermal Controls recommends that the system be tested per the
"Cable testing and maintenance" section below.
• Plug the heating cable into a 120 V ground-fault protected outlet.
• Check the circuit breaker to verify power to the cable.
• Standing water in the pipe should feel warm within an hour.

Publicité

loading