Figure 10 Jumper settings
1 Input 1 configuration jumpers
2 Input 2 configuration jumpers
3 Input 3 configuration jumpers
1. Open the controller cover.
2. Feed the wires through the cable gland.
3. Adjust the wire as necessary and tighten the cable gland.
4. The jumpers are positioned immediately behind the connector. Remove the connector for
improved access to the jumpers and configure the jumper settings according to the type of input
as shown in
Figure
5. Close the controller cover and tighten the cover screws.
6. Configure inputs in the controller.
Note: In switch input mode the controller supplies 12 volts to the switch and is not isolated from the controller. In
voltage input mode the inputs are isolated from the controller (user input voltage from 0 to 30 volts).
Connect a digital sc sensor
Note: To connect an analog sensor, refer to the instructions supplied in the module or sensor manual.
A digital sc sensor can be connected to the controller using the keyed quick-connect fitting
(Figure
11). A digital sensor can be connected with the controller powered on or off.
When a sensor is connected with the controller powered on, the controller does not automatically
perform a device scan. To make the controller perform a device scan, navigate to the
Test/Maintenance menu and select Scan Devices. If a new device is found, the controller performs
the installation process without further user action.
When a sensor is connected with the controller powered off, the controller will perform a device scan
when it is powered on again. If a new device is found, the controller performs the installation process
without further user action.
Retain the connector cap to seal the connector opening in case the sensor must be removed.
10.
4 Jumpers positioned to the left for switch inputs
5 Jumpers positioned to the right for voltage inputs
English 21