3.5. Operation Test and Installation Instruction
3.5.1. Start Up in Normal Mode
1. Open the terminal block cover on the rear panel (refer to 2.3.2). Before start the
installation, please make sure the grounding is connected properly.
2. Make sure Utility breaker, UPS' Utility breaker and Bypass breaker are on "Off" position.
3. Make sure the voltage of Utility matches with the input voltage window of the UPS.
4. Connect the Utility separately to the terminal blocks of UPS' Utility and Bypass Inputs (If
not common). Switch on the Power Breaker of the distribution panel and the breakers
of the UPS' Utility and Bypass Inputs, and then the UPS starts up. Green LEDs
light up to show the Utility and Bypass Inputs are normal and the LCD display with
parallel function will illustrate from drawing A1, drawing A2 to drawing B. Otherwise the
LCD display will illustrate from drawing A2 to drawing B.
A1
B
5. Then, the UPS is on Bypass Mode now and it will proceed self-test automatically. If
there is no abnormal message occurred, it means the pre-startup of the UPS is
successful and the charger starts to charge the batteries.
6. Press the UPS On Switch
the LCD display changes from drawing B to drawing C.
7. Then, the UPS is under self-test mode again, the LCD display will illustrate from drawing
C to drawing D and remain approx. 4 seconds under battery mode, then illustrate from
drawing E1 to drawing F if the self-test is successful.