7. Specifications
NPUT
Voltage Range (VAC)
Frequency (Hz)
Number of phases
Input Power factor
THD
OUTPUT
Voltage Range (Vac)
Voltage adjustment
Voltage regulation
Capacity
Power Factor
Output wave form
Frequency stability
Frequency regulation
Transfer time
Crest factor
Efficiency
Nominal autonomy
Cold start
BATTERY
Capacity
Quantity
Voltage (V)
Recharge time
DISPLAY
Status on LCD and LED
Data specified on LCD
Self-diagnostics
PROTECTION
Short circuit
Over heating
Low battery
EPO
Battery
Leakage current
ALARMS
Acoustics & display
PHYSICALS CHARACTERISTICS
Mechanicals dimensions
(H x W x D) mm
Net weight + battery weight
Input & Output connectors
ENVIRONMENT
Operating temp, range
Warning temperature
Altitude
Humidity
Noise
INTERFACE COMPUTER
Type
Slots
compatible systems
COMPLIANCE
Security
Standard EMC
Marking
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
57
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 11 11 AA 68 203 16
E6 LCD 5000 RT
E6 LCD 6000 RT
5000 VA / 4500 W
6000 VA / 5400 W
> 3 min
12V / 5 Ah
4 hours at 90%
Normal, Battery, Eco mode, Bypass, Battery low, Default battery, Overload and Inverter default
Input voltage and frequency, Output voltage, Frequency voltage, Charge level, Voltage battery, internal Temperature
In mains mode, from control panel , by software and auto test/ 24h
Mains mode : Bypass Transfer - Battery Mode : Automatic shutdown
176 x 440 x 680 (4U)
88 x 440 x 680*(2U)
52 Kg
Battery design for use at 25°C. A higher ambient temperature will decrease its life span
IEC/EN 62040-2 class A ; IEC/EN 61000-4-2/-3/-4/-5/-6/-8 ; IEC/EN61000-2-2 ; IEC/EN 61000-3-2/-3
E6 LCD 8000 RT
160 - 280
45 / 65 Hz
Single phase + ground
> 0,99 (full load)
<7%
200 / 208 / 220 / 230 / 240 adjustable (120 VAC optional)
Nominal voltage + 1%, + 2%, + 3%, - 1%, - 2%, - 3%
± 2%
8000 VA / 7200 W
0,9
Sine wave, THD <3% (from 0 up to 100% of load)
± 0,2% (battery mode)
+/-1Hz or +/-3Hz (programmable by user)
0 ms
3:1
Up to 90% (normal mode) ; Up to 95% (Eco mode)
> 8 min
Yes
12 V/ 7 Ah
12 V/ 7 Ah
240
Off mode immediately
Alarm and automatic stop
Switch off immediately
Electronic system of management of battery discharge
< 3 mA in full load
Mains default / Low battery / Overload / Environment default
132 x 440 x 680* (3U)
24+68 Kg
26+68 Kg
Terminal board
0-40°C
0-2000 m up to 40°C / 3000 m up to 35°C
90% max without condensation
< 50dB (at 1 m)
Standard RS 232
Second RS 232, USB, RS 485, relay card, SNMP/ Web card
Windows 95/98/NT/2000/XP/Vista, Novell Netware, Linux etc
EN62040-1-1, UL1778
CE, cUL
E6 LCD 10K RT
10000 VA / 9000 W
> 5 min
20
5 hours at 90%
132 x 440 x 680* (3U)
26+68 Kg
E6 LCD 10K RT TM
277 - 485
Three phase, R, S, T +
Neutral + Ground
<30%
10000 VA / 9000 W
12 V/ 9 Ah
52 Kg
*UPS without battery bank