6 . T E C H N I C A L S P E C I F I C A T I O N
Technology
Capacity
Power Factor
PHYSICAL CHARACTERISTICS
Dimensions L x l x h (mm) – UPS (2U)
Net Weight (kg) - UPS
INPUT
Voltage
Input nominal voltage
Frequency Range
OUTPUT
Voltage
Voltage Regulation
Frequency Range (Synchronized Range)
Frequency Range (Batt. Mode)
Current Crest ratio
Harmonic distorsion
Transfer Time
Waveform
IEC outlets standards
EFFICIENCY
AC mode
Battery mode
Eco mode
BATTERY
Battery charger
Charging current
Battery type
Batt specs & Number
Typical Recharge Time
Charging voltage
Backup time
INDICATORS
LCD display
ALARMS
Battery Mode
Low Battery
Overload
Fault
MANAGEMENT / COMMUNICATION
Communication
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
26
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 01 16 AA 59 204 03
Line mode to Battery
mode
Inverter to Bypass
E3 PRO
1000 RT
On Line Double Conversion
1000 VA/900W
310 x 438 x 88
12.7
110/115/120/127VAC or 208/220/230/240 VAC*
60-145 VAC or 120-300 VAC at 50% load
90-145 VAC or 180-300 VAC at 100% load
110/115/120/127VAC or 208/220/230/240 VAC*
47~ 53 Hz or 57 ~ 63 Hz
50 Hz ± 0.25 Hz or 60 Hz ± 0.23 Hz
≦ 3 % THD (Linear Load)
≦ 6 % THD (Non-linear Load)
3 (10A)
88%
83%
93%
Operates when UPS connected to mains
Adjustable from 1 to 3.5A
12 V9 AH
2
4 hours recover to 90% capacity
27.4VDC ± 1%
From 5 to 30 min. depending on the connected load
Load level, Battery level, AC mode, Battery mode, Bypass mode,
and Fault indicators
Sounding every 4 seconds
Sounding every second
Sounding twice every second
Continuously sounding
USB Port and RS232 & Infopower software included (support
Windows family, Linux, Unix et MAC)
E3 PRO
2000 RT
2000 VA/1800W
0,9
410 x 438 x 88
19
40-70 Hz
± 1%
03:01
0ms
0ms
Pure Sinewave
4 (10A)
89%
87%
94%
12V9Ah
4
54.7 VDC ±1%
E3 PRO
3000 RT
3000 VA/1800W
630 x 438 x 88
29,3
4 (10A)+terminal
90%
88%
95%
12V9Ah
6
82.1 VDC ±1%