8: Autonomy limitation setting
Interface
09: Charge current setting and battery capacity
Interface
In the case of connected
batteries :
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 01 16 AA 59 204 03
Setting
Parameter 2: Set up backup time on battery mode for
general outlets. (unit:minute)
0-999: setting the backup time in minutes from 0-999
for general outlets on battery mode.
999: Disable the autonomy limitation and the backup
time will depend on battery capacity. (Default)
Note: When setting as "0", the backup time will be
only 10 seconds.
Setting
Parameter 2: Set up the total battery Ah of the UPS.
(unit:Ah)
7-999: setting the total battery capacity from 7 to 999
in AH. Please set the correct battery total capacity if
external battery bank is connected.
If one or more external battery bank are connected to
the UPS, enter the total capacity of connected
batteries.
For example, if an external battery bank contains 2
9Ah batteries rows, then consider a total of 3 battery
rows that's to say : 1 for UPS + 2 for battery bank
= 3 x 9 = 27Ah).
The program setting should be adjusted from 9 to 27.
19