Dimensions in mm
X = fixing dimensions
Terminal box GHG 731 01
Terminal box GHG 731 02
Terminal box GHG 731 03
Terminal box GHG 731 11
Terminal box GHG 731 12
6 6 6 6 6
Cooper Crouse-Hinds GmbH
1

Technical data

Terminal box GHG 731
Marking acc. to 94/9/EC:
EC type examination certificate:
Rated voltage:
Rated current:
Perm. ambient temperature:
Special versions permit deviating temperature ranges.
Perm. storage temperature in original packing:
Protection category acc. to EN/IEC 60529:
Insulation class acc. to EN/IEC 61140:
Supply terminal:
GHG 731 01, GHG 731 02, GHG 731 03
GHG 731 11
GHG 731 12
Cable entries:
Test torques:
Cover screws
Cap nut of the M12 entry
Cap nut of the M16 entry
Cap nut of the M20 entry
Cap nut of the M25 entry
Cap nut of the M32 entry - M63 entry
Empty weight:
GHG 731 01
GHG 731 02
GHG 731 03
GHG 731 11
GHG 731 12
II 2 G Ex de ia/ib [ia/ib] II C T6
II 2 D Ex tD A21 IP66 T80°C
PTB 99 ATEX 1044
up to 690 V
acc. to table on the inside of the enclosure cover
-20° C up to +40° C (catalogue version)
-40° C up to +80° C
IP 66 (catalogue version)
I - with internal earth plate
II - is complied with by the terminal boxes
acc. to customers specification and as certificate
max. 4.0 mm²
max. 16.0 mm²
max. 16.0 mm²
acc. to customers specification and as certificate
2.50 Nm
1.65 Nm
2.50 Nm
2.50 Nm
3.50 Nm
5.00 Nm
approx. 0.25 kg
approx. 0.35 kg
approx. 0.45 kg
approx. 0.77 kg
approx. 0.92 kg