INSTALLATION (cont.)

INSTALL THE OUTDOOR UNIT

10
• Install the connection tube
1. Align the center of the tubing flare with the
relevant valve.
2. Screw in the flare nut by hand and then tighten
the nut with spanner and torque wrench. See
the table below for the correct torque.
3. Connecting tube specifications are shown
below:
Specifications
Design Length
Extra Refrigerant Charge
Per Ft. Above Design Length
Outer Diameter Liquid Pipe
Outer Diameter Gas Pipe
Max. Distance Height
Max. Distance Length
NOTE: Exceeding tightening torque will damage
the copper tubing.
Tightening torque table
Tubing OD
1/4"
3/8"
1/2"
5/8"
Flare nut
NOTE: To prevent wind and pest infiltration,
seal holes around the tubing and wiring with
the supplied sealer.
Installation Instructions
10,000/14,000
20,000
BTU Units
BTU Units
20 ft.
26.2 ft.
0.16 oz./ft.
0.54 oz./ft.
1/4"
3/8"
1/2"
5/8"
33 ft.
33 ft.
68 ft.
98 ft.
Tightening torque (in./lb.)
140–170
270–310
440–480
530–570
Spanner
Joint
Torque wrench
PURGE THE AIR AND
11
TEST FOR LEAKAGE
1. Install the connecting tubes of the
indoor/outdoor unit.
2. DO NOT OPEN THE GAS VALVES UNTIL THE
EVACUATION PROCESS IS COMPLETE.
3. Remove the gas line service port cap and
connect the gas valves of the vacuum gauge,
vacuum pump and outdoor unit.
NOTE: Connect by using a 1/4" Female x
1/2" Male Adapter Access Fitting (obtain locally).
4. Start the vacuum pump. (Running time should
be more than 15 minutes.)
5. Check the vacuum with the vacuum gauge. The
gauge should read -30 in. Hg. After evacuation,
fully close the handle on the manifold valve
(on the vacuum pump device). Then stop the
vacuum pump and disconnect it.
6. The pressure should be kept for 1–2 minutes
to confirm that the reading of the vacuum
gauge does not change. The pressure should
be -30 in. Hg.
7. Remove the vacuum line and replace the service
port cap.
8. Remove both the liquid and gas valve caps.
9. Open the gas and liquid valve entirely, using
the 5 mm Allen wrench. If this is not done, the
performance will be reduced, or an error will
occur.
10. Replace the caps and tighten securely.
Cap
Liquid tube
15
Vacuum gauge
Vacuum pump
Gas tube