DW-200 shown.
DW-100 has a single
button and the
Ultrasonic sensitivity
adjustment trimpot is
in a slightly different
position.
Sensor Adjustment
Remove the wall plate. Remove the button cap by firmly squeezing together the top sides of the button assembly. Gently pull it away
from the unit.
When the adjustments are completed, replace the button cap by inserting its hinges into the tabs on the main unit and then squeeze the
top of the button while pressing it into the unit. Reinstall the cover plate.
Light Level Adjustment
The light level can be set with loads ON or OFF. To enable light level control and set the threshold:
1. Make sure the room is lit appropriately.
2. Put the sensor into TEST mode. You have 5 minutes to complete the procedure.
3. Press and hold the ON/OFF button (Relay 1 button on the DW-200) for 3 seconds, until you hear a beep.
4. Step away from the sensor. After 25 seconds a beep sounds, indicating that the threshold level is set. This threshold is retained,
even if power is lost, until it is re-set or disabled. In the DW-200, light level control only affects Relay 2.
To disable light level control, press and hold the ON/OFF (Relay 1) button for 7 seconds, until a double beep tone sounds.
Reset to Default
Use the DIP Switch Settings tables on the previous page to return features to factory settings. To reset the DW press and hold the
ON/OFF (Relay 1) button for 10 seconds, until a triple beep sounds. This resets the sensor and disables light level control (the brightest
ambient light will not hold the light OFF).
Service Mode
To enter service mode set the ultrasonic trimpot to MIN (Fully counter-clockwise).
DIP SWITCH SETTINGS
1 2
Time Delay
Test/20 min
5 minutes
15 minutes
30 minutes
3
Walk-Through
Enabled
Trigger
Disabled
Mode
Standard
4
PIR Sensitivity
Option A
Low, 50%
Option B
High
Option C
=ON =OFF
Button
Hinges
Tabs
On Mode
Time
Trigger
Relay 1
Delay
Mode
Relay 2
ON
1
2
3
4
5
6
7
8
9
Walk-Through
Audible Alerts
PIR Sensitivity
5 6
Both
Either
Either
PIR
Either Either
PIR
PIR
PIR
Both Both Both
ADJUSTMENTS
4
7
Audible Alert
Enabled
Disabled
8
Relay 1 On Mode
Manual On
1
Auto On
2
DW-200 only:
9
Relay 2 On Mode
Manual On
Auto On
Factory Settings:
All models
DW-100 series
1
DW-200 series
2
ON/OFF Buttons
Relay 1
Relay 2
Ultrasonic Sensitivity
Adjustment Trimpot
DIP Switches
Ultrasonic Cones
Detection LEDs
Red = PIR
Green = Ultrasonic
PIR Lens