SIL A Relais de Protection: Surintensité et Courant de défaut terre MANUEL D’UTILISATION SER´S MANUAL FR_FANOXTD_MANU_SIL_Ocefprimarydist_SILA_R019.Docx...
Fonction 51N. Surintensité de temps inverse de neutre ..........44 4.5. Fonction 46. Surintensité instantanée de séquence négative........45 4.6. Function 49. Thermal image protectcion ................ 46 4.6.1. Curbes ............................ 47 Fonction 52. Surveillance de l’interrupteur ..............48 4.7. www.fanox.com Rev.19 2/301...
Page 3
6.2. Résistance thermique ..................... 115 6.3. Normes ..........................116 COMMUNICATION AND HMI ..............119 7.1. Communications révision A ................... 119 7.1.1. Communication frontale. RS232 ................... 119 7.1.2. Communication arrière ....................119 7.2. Communications révision B ................... 121 www.fanox.com Rev.19 3/301...
Page 4
Codes de fonction ......................228 Exceptions et réponses d’erreur ................... 228 8.1.3. 8.1.3. Types de données ......................228 8.1.5. Carte de mémoire SIL A Révision A ................229 8.1.6. Carte des états généraux ....................232 8.1.7. Carte des compteurs ..................... 232 8.1.8.
Page 5
Exceptions et réponses d’erreur ................... 252 8.2.3. 8.2.4. Types de données ......................252 8.2.5. Carte de mémoire SIL A Révision B ................253 Carte de manœuvre ...................... 261 8.2.6. 8.2.7. Exemple de cadre ModBus xamples ................262 IEC 60870-5-103 PROTOCOLE .............. 263 9.1.
À la réception des relais, il faut examiner le matériel afin de vérifier q’ils n'ont pas été endommagés pendant le transport. En cas de détérioration, il faudra en informer immédiatement le transporteur et FANOX. Les relais qui ne sont pas utilisés immédiatement devront être replacés dans leurs emballages d'origine.
Auparavant, et afin d’éviter le risque de décharge électrique, toutes les sources d’alimentation électrique doivent être éliminées. Ce produit doit être mis au rebus de manière sécurisée en évitant son incinération et tout contact avec des sources d’eau comme les rivières, les lacs, etc. www.fanox.com Rev.19 7/301...
Le secteur de l’énergie connaît une transformation profonde au niveau mondial en raison de la demande élevée en énergie : plus de lignes de distributions sont requises avec des systèmes de surveillance avancés. Face au besoin de créer des infrastructures intelligentes, FANOX a conçu la gamme SIL pour remplir cette fonction.
Page 34
Le port RS232 permet la connexion d’un PC et le contrôle de l’équipement en utilisant le programme de communication SICom (fourni par FANOX). Le port arrière RS485 permet l’intégration de l’équipement au système (SCADA). Le protocole utilisé pour les deux ports est le www.fanox.com...
électriques et des centres de transformation et de distribution, industriels ou publics. Les principales caractéristiques de l’équipement sont indiquées dans la liste ci-dessous ; ces listes seront expliquées dans le manuel: www.fanox.com Rev.19 35/301...
Page 36
Déclenchement externe Protection de surcharge thermique Optional 74CT Surveillance du transformateur de courant Indisponible optionnel Undercurrent Indisponible optionnel 46BC Détection de conducteur cassé Indisponible optionnel Protection de sectionneur de coupure par Indisponible optionnel Trip block blocage de l’enclenchement www.fanox.com Rev.19 36/301...
Page 37
2 RS485: ModBus 1 port RS485: ModBus RTU ou IEC RTU et IEC 60870- 60870-5-103 Port arrière 5-103 1 RJ45: IEC61850, DNP3.0 ou IEC 1 RS485 ModBus 60870-104 RTU et 1RJ45: IEC 61850, DNP3.0 ou IEC 60870-104 www.fanox.com Rev.19 37/301...
Page 38
3 setting tables 4 setting tables By Inputs Mechanical 4U x 1 4 ⁄ rack Dimensions 4U x ½ rack *Les événements enregistrés dans la FRAM seront conservés en cas de défaut d’alimentation comme mémoire non volatile. www.fanox.com Rev.19 38/301...
MECHANICS LPCT model: 4U x ½ Rack Standard model: 4U x ½ Rack LPCT & Standard: 4U x ¼rack LANGUAGE English, Spanish and German English, Spanish and Turkish English, Spanish and French English, Spanish and Russian RÉVISION www.fanox.com Rev.19 40/301...
0.5A or 2.5A 0,05-15 A/0,25-75 A 0.5A or 0.1A 0,01-3A/0.05-15A PRÉCISION CHARGE RELAIS 5P10 1,5 VA SIL-A/1 5P20 1,5 VA SIL-A/1 5P30 1,5 VA SIL-A/1 5P10 1,5 VA SIL-A/5 5P20 1,5 VA SIL-A/5 5P30 1,5 VA SIL-A/5 www.fanox.com Rev.19 41/301...
« Temps de fonctionnement ». Si une courbe est sélectionnée lors du réglage de la courbe (inverse, très inverse ou extrêmement inverse), le temps de fonctionnement dépend des réglages des courbe, dial et seuil. www.fanox.com Rev.19 42/301...
L’activation de la fonction de produit à 100 % de l'entrée réglée et la désactivation à 95 %. Le type de réarmement est instantané. La précision du temps de fonctionnement équivaut au temps ajusté plus un maximum de 30 ms. www.fanox.com Rev.19 43/301...
La précision du temps d’intervention est de ± 5 % ou ± 30 ms, le plus important étant appliqué, sur le temps théorique d’intervention. Les courbes utilisées avec IEC 60255-151 et ANSI IEE, sont décrites au paragraphe «Courbes». www.fanox.com Rev.19 44/301...
La précision du temps d’intervention est de ± 5 % ou ± 30 ms, le plus important étant appliqué, sur le temps théorique d’intervention. Les courbes utilisées avec IEC 60255-151 et ANSI IEE, sont décrites au paragraphe «Courbes». www.fanox.com Rev.19 45/301...
Ce sont les différents états de l’automate de l’interrupteur Défaut d’ouverture Fermé Temps de fermeture Défaut de fermeture Nombre d’ouvertures configuré Activé si le compteur de nombre d’ouvertures dépasse le réglage « Dépassement du nombre d’ouvertures » dépassé www.fanox.com Rev.19 48/301...
Page 49
52a de l’interrupteur sur l'entrée logique « Entrée 52a » et le contact 52b de l’interrupteur sur l'entrée logique « Entrée 52b ». L’automate de l’interrupteur est doté de huit états : début, ouvert, fermé, erreur, temps d’ouverture, défaut d’ouverture, temps de fermeture et défaut de fermeture. www.fanox.com Rev.19 49/301...
Ces deux paramètres sont ajustables. Lorsque cela se produit, l’état « Dépassement des ouvertures répétitives » est activé et l’événement correspondant est généré. Cette alarme se réinitialise seule lorsque le temps correspondant au nombre d’enclenchements inférieur au nombre indiqué est dépassé. www.fanox.com Rev.19 50/301...
Circuit A superv ision Circuit B superv ision Function permission Control v oltage T_UP Révision B This: Groupe Description Minimum Maximum Intervalle Unité Défaut Supervision du circuit de déclenchement 74TCS OUI/No Autorisation Temps 0,02 300,00 0,01 2,00 fonctionnement www.fanox.com Rev.19 52/301...
0,01 180,00 Refermer 4 fois 0,02 300,00 0,01 180,00 Refermer 5 fois 0,02 300,00 0,01 180,00 Tenir le temps 0,02 300,00 0,01 10,00 Temps de remplacement 0,02 300,00 0,01 10,00 Heure d'ouverture finale 0,02 300,00 0,01 10,00 www.fanox.com Rev.19 53/301...
Page 54
Wait Reclose Condition No Hold Time Hold TimeOut Time Reclose Condition Input Close TimeOut Time 52 Close Reset TimeOut Time 52 Close & 79 Unblock Command Safety TimeOut Time LOCKOUT 52 Open 79 Block Input + 79 Block Command www.fanox.com Rev.19 54/301...
Time to deactivate In < 10% Time Out incrementing Time Out In > 10% Cold Load Pickup In < 10% Time Out Time Out Time to activate In > 10% incrementing Time to activate decrementing In < 10% www.fanox.com Rev.19 55/301...
Page 56
Révision B Groupe Description Minimum Maximum Intervalle Unité Défaut Cold Load Pickup Autorisation OUI/No Groupe de réglage Pas de temps 0.02 300.00 0.01 de chargement Temps de chargement à 0.02 300.00 0.01 froid www.fanox.com Rev.19 56/301...
L’activation de la fonction de produit à 100 % de l'entrée réglée et la désactivation à 95 %. Le type de réarmement est instantané. La précision du temps de fonctionnement équivaut au temps de réglage le plus proche de 30 ms. www.fanox.com Rev.19 57/301...
Pour résoudre ces situations, l’enclenchement est bloqué lorsque le courant de phase dépasse une valeur ajustée. Groupe Description Minimum Maximum Intervalle Unité Défaut Blocage rupteur Blocage Oui/non Limite blocage 20,00 0,01 7,00 nominale www.fanox.com Rev.19 58/301...
4.16. Réglages généraux Révision A Groupe Description Minimum Maximum Intervalle Unité Défaut Réglages généraux Identification de l’appareil “fanox.com” Relation TC phases 2000 Relation TC Neutre 2000 Fréquence 60/50 Langue English Table active Adresse distante (*) Baudrate à distance (*) 4800...
Page 60
Le réglage de la fréquence est de lecture seule. La fréquence de l’équipement est sélectionnée dans la liste des modèles. Les autres réglages peuvent être réalisés indistinctement, à partir du HMI ou des communications. Toute modification des réglages suppose la réinitialisation des fonctions, qu’elles soient activées ou pas. www.fanox.com Rev.19 60/301...
0.5 A or 0.1 A A transformer with a suitable current must be used to ensure correct operation. . Fréquence Rated 50 Hz or 60 Hz. ± 3 Hz Résistance thermique Four fois le courant nominal de manière www.fanox.com Rev.19 70/301...
Page 72
In 110A In 600 A In 600A In 120A In 650 A In 650A In 130A In 700 A In 700A In 140A In 750 A In 750A In 150A In 800 A In 800A In 160A www.fanox.com Rev.19 72/301...
événements sont effacés (à partir du HMI ou des communications). • Activité MMI: cet état est activé si une touche a été enfoncée au cours des quinze dernières minutes. • Communication locale: cet état est activé si une communication est détectée sur le port avant RS232. www.fanox.com Rev.19 73/301...
Page 74
50 Hz network frequency Activation/désactivation bit-15 Erreur de mesure Erreur de mesure Activation/désactivation bit-16 Ready Ready Activation/désactivation bit-17 Erreur de protection Erreur de protection Activation bit-18 Changement de réglages Changement de réglages Activation/désactivation bit-20 Réglage Date-heure Réglage Date-heure Activation/désactivation www.fanox.com Rev.19 74/301...
Page 75
Démarrage de neutre Neutral pick-up Démarrage de phase A Phase A pick-up Démarrage de phase B Phase B pick-up Démarrage de phase C Phase C pick-up Démarrage de phase General pick-up Enclenchement de phase Enclenchement de phase www.fanox.com Rev.19 75/301...
Page 76
51P Enclenchement de A Activation Courant phase A Bit-09 51P Enclenchement de B 51P Enclenchement de B Activation Courant phase B Bit-10 51P Enclenchement de C 51P Enclenchement de C Activation Courant phase C Bit-11 51P Enclenchement 51P Enclenchement Activation www.fanox.com Rev.19 76/301...
Page 77
79 Temps Réinitialisier. Activation nombre de réenclenchement Bit-06 79 Lockout 79 Lockout Activation/désactivation nombre de réenclenchement Bit-07 79 Temps de sécurité 79 Temps de sécurité Activation nombre de réenclenchement 79 Temps dóuverture 79 Temps dóuverture Bit-08 Activation finale finale www.fanox.com Rev.19 77/301...
Page 81
Identificateur de Bit-21 Débloquer 79 Débloquer 79 Activation commande Identificateur de Bit-22 PAS de téléconduite PAS de téléconduite Activation commande Identificateur de Bit-23 Telecontrol OUI Telecontrol OUI Activation commande Identificateur de Effacer 86 Effacer 86 bit-24 Activation commande www.fanox.com Rev.19 81/301...
Page 82
Enclenchement de B Bit-23 Enclenchement de C Enclenchement de neutre Bit-25 50P Enclenchement Bit-26 50N Enclenchement Enclenchement de phase Nombre de rapport Bit-14 Rapport d'erreur Activation d'erreur Activation Événements supprimés Groupe actif par entrée Activation Nombre table active. www.fanox.com Rev.19 82/301...
Page 83
50P_2 Enclenchement de A Activation Courant phase A Bit-09 50P_2 Enclenchement de B 50P_2 Enclenchement de B Activation Courant phase B Bit-10 50P_2 Enclenchement de C 50P_2 Enclenchement de C Activation Courant phase C Bit-11 50P_2 Enclenchement 50P_2 Enclenchement Activation www.fanox.com Rev.19 83/301...
Page 85
52 Erreur fermeture Activation/désactivation Temps de fermeture Alarme nombre Bit-08 Alarme nombre ouvertures Activation/désactivation ouvertures Bit-09 Alarme I2t Alarme I2t Activation/désactivation 52Excessive 52Excessive Bit-10 Activation/désactivation ouvertures/temps ouvertures/temps Bit-11 52 a 52 a Activation/désactivation Bit-12 52 b 52 b Activation/désactivation www.fanox.com Rev.19 85/301...
Page 86
Blocage de phase A Blocage de phase A Activation/désactivation Bit-01 Blocage de phase B Blocage de phase B Activation/désactivation Trip Block Bit-02 Blocage de phase C Blocage de phase C Activation/désactivation Bit-03 Blocage de phase Blocage de phase Activation/désactivation www.fanox.com Rev.19 86/301...
Page 87
Bit-26 Verrouiller 79 Verrouiller 79 Activation/désactivation Bit-27 Débloquer 79 Débloquer 79 Activation/désactivation Activation/désactivation Bit-28 74TCS Continuité A 74TCS Continuité A Activation/désactivation Bit-29 74TCS Continuité B 74TCS Continuité B Bit-30 Signal logique 1 Bit 31 Signal logique 2 www.fanox.com Rev.19 87/301...
Page 88
Débloquer 79 Identificateur de commande Activation Bit-21 Contrôle local Contrôle local Activation Identificateur de commande Bit-22 Telecontrol Telecontrol Activation Identificateur de commande Bit-23 Réinitialiser Réinitialiser Activation Identificateur de commande Bit-25 Reset TI Reset TI Activation Identificateur de commande www.fanox.com Rev.19 88/301...
À partir du HMI. Dans ce cas, il est possible de saisir la date et l’heure grâce au clavier. Le relais conservera un nouvel événement en indiquant qu’il a été synchronisé. • Le protocole. Le comportement est identique au HMI: le relais synchronise la date et l'heure et réalise un nouvel événement de synchronisation. www.fanox.com Rev.19 89/301...
50BF Init Activation 51P phase A 79 Heure d'ouverture 49 Alarme finale Activation 51P phase B Entrée 1 49 Enclenchement Activation 51P phase C Entrée 2 Enclenchement 51P phase A Entrée 3 Enclenchement 51P phase B Entrée 4 www.fanox.com Rev.19 90/301...
Page 91
Canaux analogiques = 4 Canaux digitales = 80 Oscillograph: 41458 : 2008/10/15 11:29:11:85 Date/Heure = 15 File de défaut *************************************************************** Événements de l’Oscillo *************************************************************** Indicateur Valeur Mesure1 Mesure2 Date Heure Oscillo 2008/10/15 11:29:11:90 Début Oscillo 2008/10/15 11:29:11:400 Début www.fanox.com Rev.19 91/301...
Page 92
Une oscillographie est démarrée lorsque l'état "fault init" est activé; c'est un signal logique configurable. La configuration par défaut est la suivante: Il est possible de visualiser l'oscillographie en utilisant le logiciel SICom En utilisant le logiciel SICom, il est possible de sauvegarder l'oscillo sous forme de fichier COMTRADE www.fanox.com Rev.19 92/301...
Page 93
79 Verrouillage Bloc de phase Entrée 1 49 Alarme Entrée 2 49 Enclenchement Activation 50P_1 phase A Entrée 3 79 Temps réenclenchement Activation 50P_1 phase B Entrée 4 Activation 50P_1 phase C Entrée 5 Activation 50P_2 phase A www.fanox.com Rev.19 93/301...
Page 94
*************************************************************** Indicateur Valeur Mesure1 Mesure2 Date Heure Oscillo 2016/10/15 11:29:11:90 Début Oscillo 2016/10/15 11:29:11:400 Début Une oscillographie est démarrée lorsque l'état "fault init" est activé; c'est un signal logique configurable. La configuration par défaut est la suivante: www.fanox.com Rev.19 94/301...
Page 95
Il est possible de visualiser l'oscillographie en utilisant le logiciel SICom En utilisant le logiciel SCom, il est possible de sauvegarder l'oscillo en tant que fichier COMTRADE www.fanox.com Rev.19 95/301...
Erreur Init Bloc 50P Bloc 50N Réinitialiser Groupe de paramètres 1 Groupe de paramètres 2 79 Init 79 Activer 79 Bloc Verrouiller 79 Débloquer 79 74TCS Continuité A 74TCS Continuité B Signal logique 1 Signal logique 2 www.fanox.com Rev.19 96/301...
Pour chaque sortie il y a une PORTE LOGIQUE. Il peut effectuer une opération logique jusqu'à 16 états binaires pour obtenir un autre résultat binaire. Dans V1 de l'automate, les PORTES LOGIQUES supportées par SIL-A (adaptation A) sont: LOGIQUE DE PORTE HMI SYMBOL OR_LACTH NOR_LACTH www.fanox.com Rev.19 98/301...
Sortie 4 Déclenchement externe Début 50BF Début de la panne Bloc 50P Bloc 50N / G SIGNAUX LOGIQUES Réinitialiser Groupe de paramètres 1 Groupe de paramètres 2 Continuité A Continuité B Signal logique 1 Signal logique 2 www.fanox.com Rev.19 101/301...
Page 102
4 états binaires pour obtenir un autre résultat binaire. En V3 de l'API, les GATES LOGIQUES supportées par SIL-A (adaptation B) sont: LOGIQUE DE PORTE HMI SYMBOL NOR4 OR4_LACTH Φ NOR4_LACTH OR4_PULSES AND4 & NAND4 § AND4_PULSES OR_TIMER_UP NOR_TIMER_UP AND_TIMER_UP NAND_TIMER_UP OR_PULSE NOR_PULSE AND_PULSE NAND_PULSE www.fanox.com Rev.19 102/301...
Page 104
79 Permission pas configuré Niveau 79 Lock pas configuré Serrure Pulse 79 pas configuré Pulse 79 déverrouiller Continuité A pas configuré Continuité B pas configuré Signal logique 1 pas configuré Signal logique 2 pas configuré www.fanox.com Rev.19 104/301...
Problème de mémoire eeprom, un tableau est corrompu Erreur d’enregistrement des événements Erreur des événements D’autre part, « Ajustement par défaut » indique que le relais fonctionne avec les ajustements en usine, et toutes les fonctions de protection sont désactivées www.fanox.com Rev.19 105/301...
PAS de téléconduite ✓ ✓ ✓ Effacer 86 ✓ ✓ ✓ Effacer TI Pour exécuter les commandes à partir des communications à distance (ModBus, IEC60870-5-103, IEC61850 ou DNP 3.0 selon le modèle), l'équipement doit être en mode TELECONTROL. www.fanox.com Rev.19 106/301...
Cette horloge peut être synchronisée de deux manières: • À partir de l’interface hmi. Dans ce cas, il est possible d’introduir la date et l’heure via clavier. Le relais gardera un nouvel évènement indiquentt que celui-ci a été synchronisé. • Protocole. www.fanox.com Rev.19 107/301...
Temps d’opération: IEC Inverse curve, IEC trés inverse Temps d’opération: courbe inverse, courbe trés curve,IEC extrèmement inverse curve IEC l'inverse de inverse, courbe extrèmement inverse longue durée, IEEE Inverse curve, IEEE trés inverse curve, IEEE extrèmement inverse curve. www.fanox.com Rev.19 109/301...
Page 110
Dial: 0.02 to 2.20 (pas 0.01) Niveau d’activetion du courbe 110% Reposicionnement instantanée Précision du temporisation: ± 30 ms ou ± 0,5% (plus grand des deux) Niveau de reposicionnement du courbe 100% Niveau d’activetion del temps définis 100% www.fanox.com Rev.19 110/301...
Page 111
Temps fonctionnement: 0.02 to 300 s (pas 0.01 s) Présence de la tension de contrôle: -40% 74TCS Continuité de déclenchement, dans les circuits A et B Continuité de déclenchement, dans les circuits A et B Entrées spécifiques Entrées configurables www.fanox.com Rev.19 111/301...
à 20 fois le taraud ajusté. Autorisation de fonction: Oui/Non 74CT (*) Temps de fonctionnement: 0,02 à 300 s (pas 0,01 s) Indisponible Précision du temps de déclenchement: ± 30 ms ou ± 0,5% (plus grand des deux) www.fanox.com Rev.19 112/301...
1/4Rack – 4 U 1/2Rack - 4 U IP-54 on pannel 6.2. Résistance thermique • 4 fois le courant évalué continuellement. • 20 fois le courant nominal pendant 10 s. • 80 fois le courant nominal pendant 1s. www.fanox.com Rev.19 115/301...
Short field strenght for a duration of 3s. 1000 IEC 61000-4-8 A/m. Frequency 50Hz. 1.12. 100KHz damped oscillatory IEC 61000-4-18 Class 3, Repetition frequency 40Hz, Duration waves of each application 3s. Common mode: ±2.5kV. Differential mode: ±1kV www.fanox.com Rev.19 116/301...
Page 118
Declared on manual, without damage for overload continuous operation 8.4. VT Input short time IEC 60255-27 Declared on manual, without damage for 10s overload short time overloading 9. Enclosure protection IEC 60255-27 IP-54 IEC 60529 Quality Management System ISO 9001:2008 www.fanox.com Rev.19 118/301...
RS485 communication connectors. Fiber optics can be used in very aggressive environments, and they are connected by using the corresponding converters. Schéma de connexion pour un bus RS485: www.fanox.com Rev.19 119/301...
Page 120
RS485 communication connectors. Fiber optics can be used in very aggressive environments, and they are connected by using the corresponding converters. Schéma de connexion pour un bus RS485: www.fanox.com Rev.19 120/301...
RS485 communication connectors. Fiber optics can be used in very aggressive environments, and they are connected by using the corresponding converters. Schéma de connexion pour un bus RS485: www.fanox.com Rev.19 121/301...
Page 122
1 RJ45 pour IEC61850, DNP3.0 ou IEC60870-5-104 Dans ce cas, il existe un port RJ45 pour le protocole CEI 61850, pour le protocole DNP 3.0 ou pour le protocole CEI 60870-5-104 selon le modèle. www.fanox.com Rev.19 122/301...
• Vérifier les versions de l’appareil • Configurer l’adresse modbus 7.4.1. Comment installer le logiciel SICOM Pour installer le SICom il faut le lien suivant:: http://fanox.blob.core.windows.net/sicom/publish.htm Le lien ouvrira l'écran suivant, où la touche "install" doit être pressée: www.fanox.com Rev.19...
Dans la configuration de l’appareil au travers du logiciel SICom, il y a 4 mot de passe et leur niuveau d’accés associé. Par défaut l’appareil dispose des mots de passe suivant: NIVEAU D’ACCÈS MOT DE PASSE 2222 3333 4444 5555 www.fanox.com Rev.19 125/301...
0.00 0.00 Si une erreur est dñetecté au travers de l’autodiagnostique, apparait un message d’erreur dans la seconde ligne (Au lieu est place de “FANOX”) de l’écran qui peut être: (voir partie autodiagnostique) • ERREUR DE PROTECTION • ERREUR DE MESURE •...
0.00 0.00 À partir l’écran de repos, en appuyant la touche “▼” de manière mantenue, nous visualisons les paramétres de communication: LOCAL COM Settings SILA000C2A12BB 19200-8-N-1 0.00 0.00 0.00 0.00 LOCAL Settings 19200-8-N-1 REMOTE COM Settings ▼ www.fanox.com Rev.19 127/301...
0.00 0.00 0.00 0.00 ◄ ▼ ► OK HOLD Set Password SILA000C2A12BB -> 0 0.00 0.00 0.00 0.00 Set Password ◄▼▲► -> 5555 SILA000C2A12BB TEST MENU 0.00 0.00 0.00 0.00 Led-1: not activated Led-1: <<ACTIVATED>> www.fanox.com Rev.19 128/301...
Page 129
Led-2: ▲▼ not activated Led-2: <<ACTIVATED>> Led-3: ▲▼ not activated Led-3: <<ACTIVATED>> Led-4: ▲▼ not activated Led-4: <<ACTIVATED>> Led-5: ▲▼ not activated Led-5: <<ACTIVATED>> Led-6: not activated www.fanox.com Rev.19 129/301...
Page 130
Led-6: <<ACTIVATED>> Led-79: ▲▼ not activated Led-79: <<ACTIVATED>> Led-52: ▲▼ not activated Led-52: <<ACTIVATED>> Output 1: ▲▼ not activated Output 1: <<ACTIVATED>> Output 2: ▲▼ not activated www.fanox.com Rev.19 130/301...
Page 131
Output 5: <<ACTIVATED>> NOTE 1: SIL-A Révision B 4 sorties NOTE 2: Attention au moment de tester le Contact de Déclenchement. Quand l’appareil est installé, le circuit sera ouvert comme s’il s’agissait d’un déclenchement. www.fanox.com Rev.19 131/301...
“MESURES” puis appuyer “OK”. Avec les touches “▲” et “▼” nous nous positionnons sur la mesure et visualisons la valeur. Révision A ↑ MEASUREMENTS SILA555B1001BA 0.00 0.00 0.00 0.00 ↓ ↑ MEASUREMENTS 0.00 A ↓ 0.00 *A ▲▼ 0.00 A www.fanox.com Rev.19 133/301...
Page 134
▲▼ 0.00 A ▲▼ 0.00 A ▲▼ 0.00 A ▲▼ Révision B ↑ MEASUREMENTS SILA000C2A12BB 0.00 0.00 0.00 0.00 ↓ ↑ MEASUREMENTS 0.00 A ↓ 0.00 *A ▲▼ 0.00 A www.fanox.com Rev.19 134/301...
états. L’information disponible dans chaque état est actif ou non. Dans les Menus de groupe d’état, apparait le message “>Il y a des activations” sous le nom de groupe si certains des états contenus est actif. www.fanox.com Rev.19...
Page 136
↓ Phase A Pickup Sta. 50P1 not activated Phase B Pickup: ▲▼ not activated Phase C Pickup: ▲▼ not activated Phase Pickup: ▲▼ not activated Phase A Trip: ▲▼ not activated Phase B Trip: ▲▼ not activated www.fanox.com Rev.19 136/301...
Page 137
↓ Phase A Pickup: Sta. 50P2 not activated Phase B Pickup: ▲▼ not activated Phase C Pickup: ▲▼ not activated Phase Pickup: ▲▼ not activated Phase A Trip: ▲▼ not activated Phase B Trip: ▲▼ not activated www.fanox.com Rev.19 137/301...
Page 138
↑ STATES Sta. 51P ▲▼ ↓ Phase A Pickup: Sta. 51P not activated Phase B Pickup: ▲▼ not activated Phase C Pickup: ▲▼ not activated Phase Pickup: ▲▼ not activated Phase A Trip: ▲▼ not activated www.fanox.com Rev.19 138/301...
Page 139
▲▼ not activated Phase Trip: ▲▼ not activated ↑ STATES Sta. 50N1 ▲▼ ↓ Ground Pickup: Sta. 50G1/50N1 not activated Ground Trip: ▲▼ not activated ↑ STATES ▲▼ Sta. 50N2 ↓ Ground Pickup: Sta. 50G2/50N2 not activated www.fanox.com Rev.19 139/301...
Page 140
Ground Pickup: Sta. 51G/51N not activated Ground Trip: ▲▼ not activated Sta. CLP ↑ STATES ▲▼ ↓ Pickup: Sta. CLP not activated Sta. 50BF ↑ STATES ▲▼ ↓ Pickup: Sta. 50BF not activated Trip: ▲▼ not activated www.fanox.com Rev.19 140/301...
Page 141
▲▼ ↓ Pickup: Sta. 46 not activated Trip: ▲▼ not activated ↑ STATES Sta. 49 ▲▼ ↓ Pickup: Sta. 49 not activated Trip: ▲▼ not activated Sta. GENERAL ↑ STATES ▲▼ ↓ Trip: Sta. GENERAL not activated www.fanox.com Rev.19 141/301...
Page 142
50 Hz: ▲▼ <<ACTIVATED>> Measure error: ▲▼ not activated Setting changed: ▲▼ not activated Set Date/Time: ▲▼ not activated No Telecontrol: ▲▼ not activated FactorySetting: ▲▼ not activated Eeprom error: ▲▼ not activated Eeprom changed: ▲▼ not activated www.fanox.com Rev.19 142/301...
Page 143
▲▼ ↓ I. 52a: Sta. INPUTS not activated I. 52b: ▲▼ not activated I. 50P block: ▲▼ not activated I. 50G/50N block: ▲▼ not activated I. Ext Trip: ▲▼ not activated I. Fault. init: ▲▼ not activated www.fanox.com Rev.19 143/301...
Page 144
I. 79 Block: ▲▼ not activated I1-Sett Table: ▲▼ not activated I2-Sett Table: ▲▼ not activated Lock 79: ▲▼ not activated Unlock 79: ▲▼ not activated I. 50BF Init: ▲▼ not activated Input 1: ▲▼ not activated www.fanox.com Rev.19 144/301...
Page 145
Input 3: ▲▼ not activated Input 4: ▲▼ not activated Input 5: ▲▼ not activated Input 6: ▲▼ not activated Input 7: ▲▼ not activated Input 8: ▲▼ not activated Control Voltage: ▲▼ not activated www.fanox.com Rev.19 145/301...
Page 146
▲▼ not activated Continuity B: ▲▼ not activated Sta. OUTPUTS ↑ STATES ▲▼ ↓ LedON: not activated Led1: ▲▼ not activated Led2: ▲▼ not activated Led3: ▲▼ not activated Led4: ▲▼ not activated Led5: ▲▼ not activated www.fanox.com Rev.19 146/301...
Page 147
Output 2: Sta. OUTPUTS ▲▼ not activated Output 3: ▲▼ not activated Output 4: ▲▼ not activated Output 5: ▲▼ not activated 79 Init: ▲▼ not activated 50BF Init: ▲▼ not activated Fault Init: ▲▼ not activated www.fanox.com Rev.19 147/301...
Page 148
79 Is 52 Open?: ▲▼ not activated 79 Hold Time: ▲▼ not activated 79 Close Time: ▲▼ not activated 79 Reset Time: ▲▼ not activated 79 Lockout: ▲▼ not activated 79 Security T.: ▲▼ not activated www.fanox.com Rev.19 148/301...
Page 149
↑ STATES ▲▼ >52 Open Error ↓ 52 Startup: not activated 52 Error: ▲▼ not activated 52 Open: ▲▼ not activated 52 Open Time: ▲▼ not activated 52 Open Error: ▲▼ <<ACTIVATED>> 52 Close: ▲▼ not activated www.fanox.com Rev.19 149/301...
Page 150
Open Num. Alarm: ▲▼ <<ACTIVATED>> I2t Alarm: ▲▼ <<ACTIVATED>> Too Many Trips: ▲▼ not activated 52A contact: ▲▼ not activated 52B contact: ▲▼ not activated Sta. 74TCS ↑ STATES ▲▼ ↓ 74TCS Pickup: Sta. 74TCS not activated www.fanox.com Rev.19 150/301...
Page 151
Sta. MODBUS ↑ STATES ▲▼ ↓ Remote COM.: Sta. MODBUS not activated Command Select: ▲▼ not activated Open Breaker: ▲▼ not activated Close Breaker: ▲▼ not activated Block Recloser: ▲▼ not activated UnBlock Reclos: ▲▼ not activated www.fanox.com Rev.19 151/301...
Page 152
Sta. REMOTE ↓ Remote COM.: Sta. REMOTE not activated Command Select: ▲▼ not activated Open Breaker: ▲▼ not activated Close Breaker: ▲▼ not activated Block Recloser: ▲▼ not activated UnBlock Reclos: ▲▼ not activated Reset 86 not activated www.fanox.com Rev.19 152/301...
Page 153
↓ Local COM.: Sta. LOCAL not activated >Activated MMI Activity: ▲▼ <<ACTIVATED>> Local Ctrl.: ▲▼ not activated Command Select: ▲▼ not activated Open Breaker: ▲▼ not activated Close Breaker: ▲▼ not activated Block Recloser: ▲▼ not activated www.fanox.com Rev.19 153/301...
Page 154
UnBlock Reclos: ▲▼ not activated No Telecontrol: ▲▼ not activated Telecontrol OUI: ▲▼ not activated Reset 86 not activated www.fanox.com Rev.19 154/301...
Page 155
0.00 0.00 0.00 0.00 ↓ ↑ Sta. GENERAL STATES ▲▼ ↓ Trip: Sta. GENERAL not activated 50 Hz: ▲▼ <<ACTIVATED>> TripBlck Enab.: Not activated Measure error: ▲▼ not activated Ready: not activated Setting changed: ▲▼ not activated www.fanox.com Rev.19 155/301...
Page 156
Local Ctrl.: ▲▼ not activated FactorySetting: ▲▼ not activated Eeprom error: ▲▼ not activated Eeprom changed: ▲▼ not activated Event error: ▲▼ not activated Reset: ▲▼ not activated Pickup: ▲▼ not activated Phase A pickup: ▲▼ not activated www.fanox.com Rev.19 156/301...
Page 157
Phase C pickup: ▲▼ not activated Ground pickup: ▲▼ not activated Phase A Trip: ▲▼ not activated Phase B Trip: ▲▼ not activated Phase C Trip: ▲▼ not activated Ground Trip: ▲▼ not activated 50P Trip: ▲▼ not activated www.fanox.com Rev.19 157/301...
Page 158
↓ Phase A Pickup Sta. 50P1 not activated Phase B Pickup: ▲▼ not activated Phase C Pickup: ▲▼ not activated Phase Pickup: ▲▼ not activated Phase A Trip: ▲▼ not activated Phase B Trip: ▲▼ not activated www.fanox.com Rev.19 158/301...
Page 159
↑ STATES Sta. 50P2 ▲▼ ↓ Phase A Pickup: Sta. 50P2 not activated Phase B Pickup: ▲▼ not activated Phase C Pickup: ▲▼ not activated Phase Pickup: ▲▼ not activated Phase A Trip: ▲▼ not activated www.fanox.com Rev.19 159/301...
Page 160
Sta. 51P ↑ STATES ▲▼ ↓ Phase A Pickup: Sta. 51P not activated Phase B Pickup: ▲▼ not activated Phase C Pickup: ▲▼ not activated Phase Pickup: ▲▼ not activated Phase A Trip: ▲▼ not activated www.fanox.com Rev.19 160/301...
Page 161
▲▼ not activated Phase Trip: ▲▼ not activated ↑ STATES Sta. 50N1 ▲▼ ↓ Ground Pickup: Sta. 50N1 not activated Ground Trip: ▲▼ not activated ↑ STATES ▲▼ Sta. 50N2 ↓ Ground Pickup: Sta. 50N2 not activated www.fanox.com Rev.19 161/301...
Page 162
Ground Pickup: Sta. 51N not activated Ground Trip: ▲▼ not activated ↑ STATES Sta. 46 ▲▼ ↓ Pickup: Sta. 46 not activated Trip: ▲▼ not activated ↑ Sta. CLP STATES ▲▼ ↓ CLP Disable: Sta. CLP <<ACTIVATED>> www.fanox.com Rev.19 162/301...
Page 163
52 Def. open: ▲▼ not activated Close CLP: ▲▼ not activated Open CLP: ▲▼ not activated CLP: ▲▼ not activated Sta. 50BF ↑ STATES ▲▼ ↓ Pickup: Sta. 50BF not activated Trip: ▲▼ not activated www.fanox.com Rev.19 163/301...
Page 164
Trip: ▲▼ not activated ↑ STATES Sta. 79 ▲▼ >Lockout ↓ Standby: Sta. 79 not activated >Lockout Reclose Time: ▲▼ not activated 79 Is 52 Open?: ▲▼ not activated 79 Hold Time: ▲▼ not activated www.fanox.com Rev.19 164/301...
Page 165
79 Security T.: ▲▼ not activated 79 Manual Open: ▲▼ not activated Sta. 52 ↑ STATES ▲▼ >52 Error ↓ 52 Startup: Sta. 52 not activated >52 Error 52 Error: ▲▼ not activated 52 Open: ▲▼ not activated www.fanox.com Rev.19 165/301...
Page 166
52 Open Error: ▲▼ <<ACTIVATED>> 52 Close: ▲▼ not activated 52 Close Time: ▲▼ not activated 52 Close Error: ▲▼ not activated Open Num. Alarm: ▲▼ <<ACTIVATED>> I2t Alarm: ▲▼ <<ACTIVATED>> Too Many Trips: ▲▼ not activated www.fanox.com Rev.19 166/301...
Page 167
▲▼ not activated Sta. 74TCS ↑ STATES ▲▼ ↓ 74TCS Pickup: Sta. 74TCS not activated 74TCS Alarm: ▲▼ not activated ↑ STATES Sta. 74CT ▲▼ ↓ 74CT Pickup: Sta. 74CT not activated 74CT Alarm: ▲▼ not activated www.fanox.com Rev.19 167/301...
Page 168
▲▼ not activated Phase C Pickup: ▲▼ not activated Phase Pickup: ▲▼ not activated Phase A Trip: ▲▼ not activated Phase B Trip: ▲▼ not activated Phase C Trip: ▲▼ not activated Phase Trip: ▲▼ not activated www.fanox.com Rev.19 168/301...
Page 169
Trip: ▲▼ not activated Sta. T. BLOCK ↑ STATES ↓ Phase A block: Sta. T. BLOCK not activated Phase B block: ▲▼ not activated Phase C block: ▲▼ not activated Phase block: ▲▼ not activated www.fanox.com Rev.19 169/301...
Page 170
↑ Sta. INPUTS STATES ↓ Input 1: Sta. INPUTS not activated Input 2: ▲▼ not activated Input 3: ▲▼ not activated Input 4: ▲▼ not activated Input 5: ▲▼ not activated Input 6: ▲▼ not activated www.fanox.com Rev.19 170/301...
Page 171
↓ Output 1: Sta. OUTPUTS <<ACTIVATED>> >Activated Output 2: ▲▼ not activated Output 3: ▲▼ not activated Output 4: ▲▼ not activated ↑ STATES Sta. LEDS >Activated ↓ Led1: Sta. LEDS <<ACTIVATED>> >Activated Led2: ▲▼ not activated www.fanox.com Rev.19 171/301...
Page 172
Led3: ▲▼ not activated Led4: ▲▼ not activated Led5: ▲▼ not activated Led6: ▲▼ not activated Led-52: ▲▼ not activated Led-79: ▲▼ not activated Sta. LOGIC ↑ STATES >Activated ↓ 52a: Sta. LOGIC not activated >Activated www.fanox.com Rev.19 172/301...
Page 173
52b: ▲▼ not activated Ext Trip: ▲▼ not activated 50BF Init: ▲▼ not activated Fault Init: ▲▼ not activated Blck. 50P: ▲▼ not activated Blck. 50N: ▲▼ not activated Reset: ▲▼ not activated SettingsG1: ▲▼ not activated www.fanox.com Rev.19 173/301...
Page 174
79Init: ▲▼ not activated 79 Enable: ▲▼ not activated L Lock 79: ▲▼ not activated P Lock 79: ▲▼ not activated P Unlock 79: ▲▼ not activated 74TCS A: ▲▼ not activated 74TCS B: ▲▼ not activated www.fanox.com Rev.19 174/301...
Page 175
Sta. LOCAL STATES >Activated ↓ Local COM.: Sta. LOCAL not activated >Activated HMI Activity: ▲▼ <<ACTIVATED>> Open Breaker: ▲▼ not activated Close Breaker: ▲▼ not activated P Lock 79: ▲▼ not activated P Unlck 79: ▲▼ not activated www.fanox.com Rev.19 175/301...
Page 176
▲▼ not activated Telecontrol: ▲▼ not activated Reset: ▲▼ not activated Reset TI: ▲▼ not activated Sta. REMOTE ↑ STATES ↓ Remote COM.: Sta. REMOTE not activated Open Breaker: ▲▼ not activated Close Breaker: ▲▼ not activated www.fanox.com Rev.19 176/301...
Page 177
P Lock 79: ▲▼ not activated P Unlck 79: ▲▼ not activated Local Ctrl.: ▲▼ not activated Telecontrol: ▲▼ not activated Reset: ▲▼ not activated Reset TI: ▲▼ not activated www.fanox.com Rev.19 177/301...
Select table SETTINGS ↑ ↑ 1 = T.Activated T.A.=1 COM " ↓ ↓ Select table ↑ ▲▼ ↓ Select table ↑ ▲▼ ↓ GEN Settings 50P1 SETTINGS ↑ T.A.=1 COM ↓ Function Enable Settings 50P1 www.fanox.com Rev.19 178/301...
Page 179
Set Password ◄▼▲► -> 5555 Function Enable NO -> NO Function Enable ▲▼ NO -> OUI Function Enable NO > OUI y/n SETTING CHANGED Function Enable Function Enable Current Tap ▲▼ 1.00 xIn Operating Time ▲▼ 0.02 s www.fanox.com Rev.19 179/301...
Page 180
Function Enable Settings 50P2 Current Tap ▲▼ 0.20 xIn Operating Time ▲▼ 5.00 s SETTINGS GEN Settings 51P ↑ ▲▼ T.A.=1 COM ↓ Function Enable Settings 51P Curve type ▲▼ Def Tim Time Dial ▲▼ 0.05 www.fanox.com Rev.19 180/301...
Page 181
COM T.A.=1 ↓ Function Enable Settings 50G1/50N1 Current Tap ▲▼ 0.50 xIn Operating Time ▲▼ 1.00 s ↑ Settings 50N2 SETTINGS GEN ▲▼ COM T.A.=1 ↓ Function Enable Settings 50G2/50N2 Current Tap ▲▼ 0.30 xIn www.fanox.com Rev.19 181/301...
Page 182
COM T.A.=1 ↓ Function Enable Settings 51G/51N Curve type ▲▼ Def Tim Time Dial ▲▼ 0.05 Current Tap ▲▼ 0.20 xIn Operating Time ▲▼ 5.00 s ↑ Settings CLP SETTINGS GEN ▲▼ COM T.A.=1 ↓ www.fanox.com Rev.19 182/301...
Page 183
Settings CLP Multiplier 50P1 ▲▼ 1.00 Multiplier 50P2 ▲▼ 1.00 Multiplier51P ▲▼ 1.00 Multiplier 50G1/50N1 ▲▼ 1.00 Multiplier 50G2/50N2 ▲▼ 1.00 Multiplier 51G/51N ▲▼ 1.00 No Load Time ▲▼ 15 s Cold Load Time ▲▼ 15 s www.fanox.com Rev.19 183/301...
Page 184
0.02 s ↑ SETTINGS GEN Settings 46 ▲▼ T.A.=1 COM ↓ Function Enable Settings 46 Current Tap ▲▼ 0.20 xIn Operating Time ▲▼ 0.02 s ↑ Settings 49 SETTINGS GEN ▲▼ COM T.A.=1 ↓ www.fanox.com Rev.19 184/301...
Page 185
Current Tap ▲▼ 1.00xIn z Heating constant ▲▼ 3 min z Cooling constant ▲▼ Alarma Level ▲▼ ↑ Settings 79 SETTINGS GEN ▲▼ COM T.A.=1 ↓ Function Enable Settings 79 Hold Enable ▲▼ Recloser Number ▲▼ www.fanox.com Rev.19 185/301...
Page 186
▲▼ 0.02 s Reclose 3 Time ▲▼ 1.00 s Reclose 4 Time ▲▼ 1.00 s Reclose 5 Time ▲▼ 1.00 s Hold Time ▲▼ 1.00 s Reset Time ▲▼ 1.00 s Man. Open Time ▲▼ 1.00 s www.fanox.com Rev.19 186/301...
Page 187
Max. Open Time ▲▼ 0.10 s Max. Close Time ▲▼ 0.10 s Repetitive Open Num ▲▼ Repetitiv Open Time ▲▼ 9.00 min ↑ Settings 74TCS SETTINGS GEN ▲▼ COM T.A.=1 ↓ Function Enable Settings 74TCS www.fanox.com Rev.19 187/301...
Page 188
La fréquence du réseau est choisie en fonction du modèle. La valeur est seulement de lecture. GEN Identification ↑ SETTINGS ◄ free text COM ↓ T.A.=1 CT Phase Ratio ▲▼ CT Neutral Ratio ▲▼ VT Ratio ▲▼ www.fanox.com Rev.19 188/301...
Page 189
à l’autre. Suite à une erreur, s’il est nécessaire de changer un caractère ou un numéro du mot de passe, “C” pour l’effacer. Pour valider le mot de passe appuyer “ appuyer www.fanox.com Rev.19 189/301...
Page 190
COM " ↓ ↓ ↑ Select group ▲▼ ↓ ↑ Select group ▲▼ ↓ Select group ↑ ▲▼ ↓ GEN Sett(1) 50P1 SETTINGS ↑ COM " ↓ Function Enable Sett(1) 50P1 Set Password Function Enable -> 0 www.fanox.com Rev.19 190/301...
Page 191
Function Enable ▲▼ NO -> OUI Function Enable NO > OUI y/n SETTING CHANGED Function Enable Function Enable Current Tap ▲▼ 1.00 xIn Time Delay ▲▼ 0.02 s Sett(1) 50P2 SETTINGS GEN ↑ ▲▼ COM " ↓ www.fanox.com Rev.19 191/301...
Page 192
Current Tap ▲▼ 0.20 xIn Time Delay ▲▼ 5.00 s SETTINGS GEN Sett(1) 51P ↑ ▲▼ COM " ↓ Function Enable Sett(1) 51P Curve type ▲▼ Def Tim Time Dial ▲▼ 0.05 Current Tap ▲▼ 0.20 xIn www.fanox.com Rev.19 192/301...
Page 193
Function Enable Sett(1) 50N1 Current Tap ▲▼ 0.50 xIn Time Delay ▲▼ 1.00 s ↑ Sett(1) 50N2 SETTINGS GEN ▲▼ COM " ↓ Function Enable Sett(1) 50N2 Current Tap ▲▼ 0.30 xIn Time Delay ▲▼ 2.00 s www.fanox.com Rev.19 193/301...
Page 194
GEN Sett(1) 51N ↑ SETTINGS ▲▼ COM " ↓ Function Enable Sett(1) 51N Curve type ▲▼ Def Tim Time Dial ▲▼ 0.05 Current Tap ▲▼ 0.20 xIn Time Delay ▲▼ 5.00 s www.fanox.com Rev.19 194/301...
Page 195
Function Enable Sett(1) 46 Curve type ▲▼ Def Tim Time Dial ▲▼ 0.05 Current Tap ▲▼ 0.20 xIn Time Delay ▲▼ 5.00 s ↑ GEN Sett(1) CLP SETTINGS ▲▼ COM " ↓ Function Enable Sett(1) CLP www.fanox.com Rev.19 195/301...
Page 196
15 s ↑ Sett(1) 50BF SETTINGS GEN ▲▼ COM " ↓ Function Enable Sett(1) 50BF Time Delay ▲▼ 0.02 s ↑ Sett(1) SETTINGS GEN ▲▼ COM " ↓ Function Enable Sett(1) Current Tap ▲▼ 1.00xIn www.fanox.com Rev.19 196/301...
Page 197
Heating constant ▲▼ 3 min z Cooling constant ▲▼ Alarma Level ▲▼ ↑ SETTINGS GEN Sett(1) ▲▼ COM " ↓ Function Enable Sett(1) Hold Enable ▲▼ Recloser Number ▲▼ Reclose 1 Time ▲▼ 0.02 s www.fanox.com Rev.19 197/301...
Page 198
1.00 s Reclose 5 Time ▲▼ 1.00 s Hold Time ▲▼ 1.00 s Reset Time ▲▼ 1.00 s Man. Open Time ▲▼ 1.00 s ↑ Sett(1) SETTINGS GEN ▲▼ COM " ↓ Max Acumulated Open Sett(1) www.fanox.com Rev.19 198/301...
Page 199
0.10 s Max. Close Time ▲▼ 0.10 s Repetitive Open Num ▲▼ Repetitiv Open Time ▲▼ 9.00 min ↑ SETTINGS GEN Sett(1) 74TCS ▲▼ COM " ↓ Function Enable Sett(1) 74TCS Time Delay ▲▼ 0.02 s www.fanox.com Rev.19 199/301...
Page 200
Time Delay ▲▼ 0.02 s GEN Sett(1) 37 ↑ SETTINGS COM " ↓ Function Enable Sett(1) 37 Current Tap ▲▼ 0.20 xIn Time Delay ▲▼ 0.02 s GEN Sett(1) 46BC ↑ SETTINGS COM " ↓ www.fanox.com Rev.19 200/301...
Page 201
Function Enable Sett(1) 46BC Current Tap ▲▼ Time Delay ▲▼ 0.02 s GEN Sett(1) T. Block ↑ SETTINGS COM " ↓ Function Enable Sett(1) T. Block Current Tap ▲▼ 7xIn www.fanox.com Rev.19 201/301...
Page 202
La fréquence du réseau est choisie en fonction du modèle. La valeur est seulement de lecture. GEN Identification ↑ SETTINGS ◄ free text COM " ↓ Frequency ▲▼ 50Hz Serial number ▲▼ Language ▲▼ ENG. Active Setting G. ▲▼ Ph. Nominal Current ▲▼ www.fanox.com Rev.19 202/301...
Page 203
N. Nominal Current ▲▼ CT Phase Ratio ▲▼ CT Neutral Ratio ▲▼ Local COM Address ▲▼ Remote Address ▲▼ Remote Baudrate ▲▼ 19200 Remote Protocol ▲▼ MODBUS www.fanox.com Rev.19 203/301...
4/5: 0 ▲▼ ┐ 52 Open Error ┐ 52 Open Error Set Password EVENTS ↑ RESET -> 0 There are 5 ↓ Set Password ◄▼▲► -> 5555 Confirm Erased Events y/n? EVENTS ↑ There are 1 ↓ www.fanox.com Rev.19 204/301...
Page 205
• Déplacement de l’évènement dans la liste d’événements • Évènement généré par activation ou reposicionnement de l’état • Mesure associée (si disponible) Associated Time Event number measurement Date 01/01/00 00:54:18600 1/120 measurement EventsErased EventsErased Activated or Not activated Event Description www.fanox.com Rev.19 205/301...
“COMPTEURS” et nous informe du nombre d’événements dans le buffer. En appuyant “OK” et avec les touches “▲” et “▼” nous nous positionnons sur chacuns des événements. Révision A ↑COUNTERS SILA555B2001BA 0.00 0.00 0.00 0.00 ↓ Openings Number ↑COUNTERS ↓ Accumulated Amps ▲▼ 14011325 k(A2) Reclosing Numbers ▲▼ Thermal Image ▲▼ www.fanox.com Rev.19 206/301...
À partir l’écran de repos, en appuyant la touche “OK”, nous entrons dans la primière ligne de Menus. Avec les touches “▲” et “▼” nous nous positionnons sur l’écran d’ “MANŒUVRE” et nous informe du nombre d’événements dans le buffer. En appuyant “OK” et avec les touches “▲” et “▼” nous nous positionnons sur chacuns des événements. www.fanox.com Rev.19 207/301...
Page 208
Open Breaker Open Breaker COMMANDS ↑ ↓ EXECUTE COMMAND y/n ↑ COMMANDS ▲▼ Close Breaker ↓ CONFIRM COMMAND y/n EXECUTE COMMAND y/n Close Breaker Close Breaker COMMANDS ↑ ↓ EXECUTE COMMAND y/n ↑ COMMANDS ▲▼ Block Recloser ↓ www.fanox.com Rev.19 208/301...
I. 52a I. 52a: Not Asigned not activated I. 52a Do not Asign y/n I. 52a ▲▼ Set to Input 1 y/n? I. 52a ▲▼ Set to Input 2 y/n? I. 52a ▲▼ Set to Input 3 y/n? www.fanox.com Rev.19 217/301...
Page 218
I. 52a ▲▼ Sta. INPUTS Set to Input 4 y/n? Configuration Processing... I. 52a Asigned to Input 4 I. 52a ▲▼ Set to Input 5 y/n? www.fanox.com Rev.19 218/301...
Page 219
Sta. 50P1 > LedON y/n? Phase B Pickup: Phase B Pickup: ▲▼ ► Sta. 50P1 > Led1 y/n? > Led1 y/n? Configuration Processing... Con 1/16 Led1 Phase B Pickup Phase B Pickup: ◄ ⌠ > Led1 y/n? www.fanox.com Rev.19 219/301...
Page 220
Phase B Pickup: ▲▼ > Led5 y/n? Phase B Pickup: ▲▼ > Output 1 y/n? Phase B Pickup: ▲▼ > Output 2 y/n? Phase B Pickup: ▲▼ > Output 3 y/n? Phase B Pickup: ▲▼ > Output 4 y/n? www.fanox.com Rev.19 220/301...
Page 221
79 Init y/n? Phase B Pickup: ▲▼ > 50BF Init y/n? Phase B Pickup: ▲▼ > Osc Init y/n? Révision B States 50P ↑STATES ↓ Phase A Pickup: States 50P not activated Phase B Pickup: ▲▼ not activated www.fanox.com Rev.19 221/301...
Page 222
Led 2 y/n? Phase B Pickup: ◄ ⌠ > Led 2 y/n? Phase B Pickup: > Led 2 y/n? ◄ Phase B Pickup: Φ > Led 2 y/n Phase B Pickup: & > Led 2 y/n? ◄ www.fanox.com Rev.19 222/301...
Page 223
> Led 2 y/n? ◄ Phase B Pickup: > Led 2 y/n? ◄ Phase B Pickup: > Led 2 y/n? ◄ Phase B Pickup: > Led 2 y/n? ◄ Phase B Pickup: > Led 2 y/n? ◄ www.fanox.com Rev.19 223/301...
Page 224
Phase B Pickup: > Led 2 y/n? ◄ Phase B Pickup: ▲▼ > Led 3 y/n? Phase B Pickup: > Led 4 y/n? Phase B Pickup: > Led 5 y/n? www.fanox.com Rev.19 224/301...
Page 225
> Led-52 y/n? Phase B Pickup: > Led-79 y/n? Phase B Pickup: > Output 1 y/n? Phase B Pickup: > Output 2 y/n? Phase B Pickup: > Output 3 y/n? Phase B Pickup: > Output 4 y/n? www.fanox.com Rev.19 225/301...
La longueur de ce temps de silence varie en fonction de la vitesse de transmission et équivaut à 3 caractères. Le tableau suivant illustre le format du paquet générique valide pour la transmission et la réception. Cependant, chaque fonction disposera de ses propres particularités comme décrit plus bas. www.fanox.com Rev.19 226/301...
Un cadre est dit « terminé » lorsque rien n’est reçu sur la TEMPS MORT Temps requis pour transmettre 3,5 ligne pendant une période de 3,5 octets. C'est-à-dire : octets 15 ms à 2 400 bps 2 ms à 19 200 bps …etc. www.fanox.com Rev.19 227/301...
Exemple : 0x1A41 = 0001101001000001b BIT32 Type bits groupés, de 32 en 32. ENUM Entier sans signe de 16 bits. Chaque valeur pouvant être adoptée par cet entier disposera d’une valeur correspondante dans le tableau auxiliaire de la base des www.fanox.com Rev.19 228/301...
Nombre de mesure(UINT).Texte descriptif(ASCII7).Unité(ASCII3).Unité primaire(ASCII5).Nombre de décimales(UCHAR) GAJU Nombre de groupes(UINT).Indice du critère-1(UINT).Indice du premier ajustement du critère-1(UINT). … Indice du critère-30(UINT).Indice du premier ajustement du critère-30(UINT). 8.1.5. Carte de mémoire SIL A Révision A Adresse Nombre de Fonction Description Format registres début...
Page 230
Voir carte des états de Lecture des États de Protection PEST protection Lecture des critères de protection Voir carte de critères PCRIT implémentés par l’équipement de protection Lire les caractéristiques d’un Voir carte de critères CCRIT Critère de Protection de protection www.fanox.com Rev.19 230/301...
Page 231
Lecture d'un paramètre 3001 See Settings map Écrire d'un paramètre 3001 See Settings map Écrire -Confirmation d'un 5001 See Settings map paramètre Lire le répertoire du premier paramètre de chaque critère de 7001 GAJU See Settings map protection www.fanox.com Rev.19 231/301...
Counter to record the number of openings Accumulated amps counter: I²t Counter to record the number of reclosings Thermal Image 8.1.8. Carte des commandes Open Circuit Breaker Close Circuit Breaker Lock the recloser Unlock the recloser Reset 86 www.fanox.com Rev.19 232/301...
Page 236
Status 79 Replacement time bit-6 Status 79 in Lockout bit-7 Status 79 Safety time bit-8 Status 79 Definitive Opening Time bit-0 Status 52 Start bit-1 Status 52 Error bit-2 Status 52 Open bit-3 Status 52 Opening time www.fanox.com Rev.19 236/301...
Page 237
Local communication bit-1 HMI Activity bit-2 Local control bit-16 Command select bit-17 Open Circuit Breaker Local bit-18 Close Circuit Breaker Modbus bit-19 Lock 79 bit-20 Unlock 79 bit-21 Telecontrol No bit-22 Telecontrol OUI bit-24 Reset 86 www.fanox.com Rev.19 237/301...
50/51 Pickup up A 50/51 Pickup up B 50/51 Pickup up C 50/51 Pickup up P 50/51P 50/51 Trip A 50/51 Trip B 50/51 Trip C 50/51 Trip P 50 Pickup up N/G 50N/G_1 50 Trip N/G www.fanox.com Rev.19 238/301...
Page 239
General Telecontrol NO General factory settings General General eeprom error General Eeprom values change General events error General New Oscillography record General there are events General external trip General Measurement error General identification Active table by input www.fanox.com Rev.19 239/301...
Page 241
Status 79 Closing time Status 79 Reset time Status 79 Lockout Status 79 Safety time Status 79 Definitive Opening Time Status 52 Inicio Status 52 Error Status 52 Open Status 52 Opening time Status 52 Opening fault www.fanox.com Rev.19 241/301...
Page 242
Command select Open Circuit Breaker Close Circuit Breaker Lock 79 ModBus Unlock 79 Telecontrol NO Telecontrol OUI Reset 86 Command select Open Circuit Breaker Close Circuit Breaker Lock 79 Remote Unlock 79 Telecontrol NO Telecontrol OUI Reset 86 www.fanox.com Rev.19 242/301...
Page 244
5039 DENUM NOSI Permission 3040 5040 0,10 0,01 FLOAT nominal Operating 3041 5041 0,02 300,0 0,01 FLOAT Time SIL A xxxx0xxxx model Excessive 3042 5042 LONG Number of 10000 Openings Maximum 3043 5043 Accumulated 10000 LONG Amps 3044 5044 Opening Time...
Page 245
CLP duration 1800 1,00 3068 5068 DENUM NOSI 74TCS Permission 3069 5069 74TCS Operating time 0,02 300,00 0,01 FLOAT SIL A xxxx1xxxx model 3042 5042 DENUM NOSI Permission 3043 5043 FLOAT 2,40 0,01 Inominal ζ heating 3044 5044 www.fanox.com Rev.19...
Nombre d’Octets Clé 35,35,35,35 Checksum H Checksum L Et le SIL répondra OK : Adresse Fonction Adresse de début H Adresse de début L Nombre de registres H Nombre de registres L Nombre d’Octets Checksum H Checksum L www.fanox.com Rev.19 247/301...
Page 248
Checksum L Et le SIL répondra avec les mesures IA, IB, IC et I0 en format FLOAT: Adresse Fonction Nombre d’Octets Mesure IA 00,00,00,00 Mesure IB 00,00,00,00 Mesure IC 00,00,00,00 Mesure IN 00,00,00,00 Checksum H Checksum L www.fanox.com Rev.19 248/301...
Et le SIL répondra avec : Adresse Fonction Nombre d’Octets État 50P 00,09 État 51P 00,00 État 50N 00,00 État 51N 00,00 État général 00,00,00,D2 État Entrées 80,21 État Sorties 00,00 État COM 00,03 RÉSERVÉ checksum H checksum L 00,00,00,01,00,00,00,00,……,7C,B1,0A,AF,DD www.fanox.com Rev.19 249/301...
La longueur de ce temps de silence varie en fonction de la vitesse de transmission et équivaut à 3 caractères. Le tableau suivant illustre le format du paquet générique valide pour la transmission et la réception. Cependant, chaque fonction disposera de ses propres particularités comme décrit plus bas. www.fanox.com Rev.19 250/301...
Un cadre est dit « terminé » lorsque rien n’est reçu sur la TEMPS MORT Temps requis pour transmettre 3,5 ligne pendant une période de 3,5 octets. C'est-à-dire : octets 15 ms à 2 400 bps 2 ms à 19 200 bps …etc. www.fanox.com Rev.19 251/301...
Exemple : 0x1A41 = 0001101001000001b BIT32 Type bits groupés, de 32 en 32. ENUM Entier sans signe de 16 bits. Chaque valeur pouvant être adoptée par cet entier disposera d’une valeur correspondante dans le tableau auxiliaire de la base des www.fanox.com Rev.19 252/301...
Nombre de mesure(UINT).Texte descriptif(ASCII7).Unité(ASCII3).Unité primaire(ASCII5).Nombre de décimales(UCHAR) GAJU Nombre de groupes(UINT).Indice du critère-1(UINT).Indice du premier ajustement du critère-1(UINT). … Indice du critère-30(UINT).Indice du premier ajustement du critère-30(UINT). 8.2.5. Carte de mémoire SIL A Révision B Start Number of Function Description Format address...
Page 254
State reading Local communication in status BIT32 and events section State reading 50P1 in status and events BIT32 section State reading 50/51P in status and events BIT32 section 50N/G_1 in status and events State reading BIT32 section www.fanox.com Rev.19 254/301...
Page 255
Logoc in status and events BIT32 section State reading 37 in status and events BIT32 section State reading 46BC in status and events BIT32 section 03 and 16 Setting ASCII20 Equipment identifier 03 and 16 Setting DENUM 5060Hz Frequency www.fanox.com Rev.19 255/301...
Page 256
03 and 16 Setting FLOAT F50/51N/G Tap 03 and 16 Setting FLOAT F50/51N/G Definite time 03 and 16 Setting DENUM NOSI F49 Permission 03 and 16 Setting FLOAT F49 Tap 03 and 16 Setting LONG F49 Heating constant www.fanox.com Rev.19 256/301...
Page 257
03 and 16 Setting DENUM NO SI F79 Hold permission 03 and 16 Setting FLOAT F79 Number of reclosings F79 Reclosing 1 time 03 and 16 Setting FLOAT 03 and 16 Setting FLOAT F79 Reclosing 2 time www.fanox.com Rev.19 257/301...
Page 258
Neutral Nominal current CURRENT 03 and 16 Confirm setting FLOAT CT phase ratio 03 and 16 Confirm setting FLOAT CT neutral ratio 03 and 16 Confirm setting LONG Local address 03 and 16 Confirm setting LONG Remote address www.fanox.com Rev.19 258/301...
Page 259
DENUM NOSI F50P2 Permission Confirm setting FLOAT F50P2 Tap Confirm setting FLOAT F50P2 Operating time Confirm setting DENUM NOSI F50N/G_2 Permission Confirm setting FLOAT F50N/G_2 Tap F50N/G_2 Operating time Confirm setting FLOAT Confirm setting DENUM NOSI F46 Permission www.fanox.com Rev.19 259/301...
Page 260
F79 Def. opening time Confirm setting DENUM NO SI CLP Permission Confirm setting LONG CLP Active table Confirm setting FLOAT CLP No load time CLP cold load time Confirm setting FLOAT Confirm setting DENUM NO SI F74TCS Permission www.fanox.com Rev.19 260/301...
Confirm setting DENUM NOSI Confirm setting FLOAT F46BC Tap Confirm setting FLOAT F46BC Operating time Carte de manœuvre 8.2.6. Open Circuit breaker Close circuit breaker Pulse Lock 79 Pulse Unlock 79 Local control Telecontrol Reset Reset thermal image www.fanox.com Rev.19 261/301...
L registers And the SIL-A will reply with: Number of General Inputs Outputs address function Bytes Status Status Status Status Status Status Status Status 00,09 00,00 00,00 00,00 00,00,00,D2 80,21 00,00 00,03 RESERVED checksum H checksum L 00,00,00,01,00,00,00,00,………….…,7C,B1,0A,AF,DD www.fanox.com Rev.19 262/301...
The following functions are supported: • Initialization • General Interrogation • Synchronization • Commands transmission Information in monitor direction: <1>:= time-tagged message <2>:= time-tagged message with relative time <3>:= measurands I <5>:= identification <6>:= time synchronization <8>:= general interrogation termination www.fanox.com Rev.19 263/301...
Page 264
SE,GI <18> Protection active SE,GI <19> LED reset <20> Monitor direction locked <21> Test mode <22> Local parameter setting SE,GI <23> Characteristic 1 <24> Characteristic 2 <25> Characteristic 3 <26> Characteristic 4 <27> Auxiliary input 1 SE,GI www.fanox.com Rev.19 264/301...
Page 265
Earth fault reverse, i.e. busbar Fault indications in monitor direction <64> Pickup L1 <65> Pickup L2 <66> Pickup L3 <67> Pickup N <68> General trip <69> Trip L1 <70> Trip L2 <71> Trip L3 <72> Trip I>> (back-up operation) www.fanox.com Rev.19 265/301...
Page 266
<92> Trip IN> <93> Trip IN>> Auto-reclosure indications in monitor direction <128> CB 'on' by AR <129> CB 'on' by long-time AR <130> AR blocked SE,GI Measurements in monitor direction <144> Measurement I <145> Measurement I, V www.fanox.com Rev.19 266/301...
Page 267
SE,GI <12> 52 Status Error <16> 79 Status Reclose Time <17> 79 Status Open <18> 79 Status Wait Time <19> 79 Status Reset Time <20> 79 Status Security Time <21> 79 Status final open Time <23> Start www.fanox.com Rev.19 267/301...
Page 268
1 Setting group input SE, GI <58> 2 Setting group input SE, GI <59> 79 pulse lockout input SE, GI <60> 79 pulse unlock input SE, GI <61> 50BF init input SE, GI <62> Control voltage SE, GI www.fanox.com Rev.19 268/301...
Page 270
Unlock 79 <148> Switching selection <149> Open CB <150> Close CB <151> Lockout 79 <152> Unlock 79 <153> 49 Reset SE, GI <160> Activation SE, GI <1> 46 Start <2> 46 Trip <8> 49 Alarm <9> 49 Trip www.fanox.com Rev.19 270/301...
Page 271
37 Trip B <30> 37 Trip C <31> 37 Trip P <32> 37 Start A <33> 37 Start B <34> 37 Start C <35> 37 Start P <36> 37 Trip A <37> 37 Trip B <38> 37 Trip C www.fanox.com Rev.19 271/301...
Page 272
50 Trip C <59> 50 Trip P <60> 50 Start A <61> 50 Start B <62> 50 Start C <63> 50 Start P <64> 50 Trip A <65> 50 Trip B <66> 50 Trip C <67> 50 Trip P www.fanox.com Rev.19 272/301...
Page 273
67 Trip N <100> 67 Start A <101> 67 Start B <102> 67 Start C <103> 67 Start P <104> 67 Trip A <105> 67 Trip B <106> 67 Trip C <107> 67 Trip P <108> 67 Start A www.fanox.com Rev.19 273/301...
Page 274
27 Start B <10> 27 Start C <11> 27 Start P <12> 27 Trip A <13> 27 Trip B <14> 27 Trip C <15> 27 Trip P <16> 27 Start A <17> 27 Start B <18> 27 Start C www.fanox.com Rev.19 274/301...
Page 275
59 Trip A <33> 59 Trip B <34> 59 Trip C <35> 59 Trip P <36> 59 Start A <37> 59 Start B <38> 59 Start C <39> 59 Start P <40> 59 Trip A <41> 59 Trip B www.fanox.com Rev.19 275/301...
Page 276
SIL-A relay uses this type to send the value of the currents IL1, IL2 and IL3, the other measures remain with value 0. Each current value is in the range 0 – 4095 where 4095 corresponds to 1,2*In e.g. a received value of 806 with a nominal value In=5A corresponds to 1,18A www.fanox.com Rev.19 276/301...
Page 277
<245> data <248> Write entry <249> Write entry with confirmation <250> Write entry with execution <251> Write entry aborted Particular commands in control direction <1> CB close (1) / open (0) ACK,NACK <153> 49 Reset (0) ACK,NACK www.fanox.com Rev.19 277/301...
In the Logical Node, the starting of the unit is represented by its Data Object, Str, with a list of Data Attributes that give information about the starting: Attribute neut indicates the status of the starting, t attribute indicates the time stamp when the starting has changed, etc. www.fanox.com Rev.19 278/301...
Page 279
(PHS)PIOC1 phsA 50P_1 Start B (PHS)PIOC1 phsB 50P_1 Start C (PHS)PIOC1 phsC 50P_1 Start P (PHS)PIOC1 general 50P_1 Trip A (PHS)PIOC1 phsA 50P_1 Trip B (PHS)PIOC1 phsB 50P_1 Trip C (PHS)PIOC1 phsC 50P_1 Trip P (PHS)PIOC1 general www.fanox.com Rev.19 279/301...
37P_1 Trip A (PHS)PTUC1 phsA 37P_1 Trip B (PHS)PTUC1 phsB 37P_1 Trip C (PHS)PTUC1 phsC 37P_1 Trip P (PHS)PTUC1 general 46 Start (NGS)PTOC1 general 46 Trip (NGS)PTOC1 general 49 Alarm PTTR1 AlmThm general 49 Trip PTTR1 general www.fanox.com Rev.19 280/301...
52 Status Close Failure GGIO2 Ind8 stVal 52 Status excessive openinigs GGIO2 Ind9 stVal Status excessive sum GGIO2 Ind10 stVal switched amperes 52 Status excessive openings per GGIO2 Ind11 stVal minute 52-A Status GGIO2 Ind12 stVal www.fanox.com Rev.19 281/301...
Page 282
Continuity B GGIO3 Ind14 stVal 49 Reset GGIO3 Ind15 stVal Start SCBC1 ColFail stVal Fault init RDRE1 RcdStr stVal 52 closed Status CSWI1 stVal 52 Status Open Time CSWI1 OpOpn stVal 52 close CSWI1 OpCls stVal www.fanox.com Rev.19 282/301...
Page 284
The definition of Datasets has to be made in a IEC61850’s file with extension .ICD (IED Capability Description) that is provided with the device. By default there are 4 Datasets, grouped according the functionality (Trips, Measures, Events and Goose): Trips, with the name of Trips and the following data objects: www.fanox.com Rev.19 284/301...
Page 285
Measures, with the name of Measures and the following data objects: Events, with the name of Events and the following data objects: www.fanox.com Rev.19 285/301...
Page 286
URCB have not this time buffer and it is not possible recovering lost or past reports. They are usually used for reporting of measures. Standard SILA device is pre configured with 10 URCB associated to the Measures Dataset: 10 BRCB associated to Events Dataset and another 10 to Trips Dataset: www.fanox.com Rev.19 286/301...
Goose dataset (General Trips and Starts) into the net. One IED that requires the information from a Goose has to be configured using the ICD file from SILA. In this file appears the default parameters of the Goose message. www.fanox.com Rev.19 287/301...
13. DNP 3.0 PROTOCOLE 11.1. Device profile document DNP V3.00 DEVICE PROFILE DOCUMENT This document must be accompanied by : Implementation Table and Point List. FANOX Electronic, S.L. Vendor Name: SIL-A Device Name: Highest DNP Level Supported: Device Function: For Requests ...
Page 289
Sometimes Configurable _______________________________________________________________________ Attach explanation: All points support the same Function Codes :Direct Operate and Direct Operate-No ACK All points support the same Control Codes : Pulse ON, Latch ON, Latch OFF, Pulse OFF and Trip-Pulse ON. www.fanox.com Rev.19 289/301...
Time and Date count=1 Time Delay Fine count=1 Class 0 Data Class 1 Data 6,7,8 20,21 Class 2 Data 6,7,8 20,21 Class 3 Data 6,7,8 20,21 Internal Indications index=7 No Object (Cold Start) No Object (Warm Start) www.fanox.com Rev.19 292/301...
52 Status excessive openings per minute 52-A Status 52-B Status 52 Status Error 79 Status Reclose Time 79 Status Open 79 Status Wait Time 79 Status Reclaim Time 79 Status Security Time 79 Status final open Time Start Trip Circuit Supervision www.fanox.com Rev.19 293/301...
Page 294
50_2 Trip N 50_1 Start A 50_1 Start B 50_1 Start C 50_1 Start P 50_1 Trip A 50_1 Trip B 50_1 Trip C 50_1 Trip P 50_2 Start A 50_2 Start B 50_2 Start C 50_2 Start P www.fanox.com Rev.19 294/301...
Page 295
In SIL-A relay, the value of the currents IL1, IL2 and IL3 have valid values, the other measures remain with value 0. Each current value is in the range 0 – 4095 where 4095 corresponds to 1,2*In e.g. a received value of 806 with a nominal value In=5A corresponds to 1,18A www.fanox.com Rev.19 295/301...
79 Status Wait Time 79 Status Reclaim Time 79 Status Security Time 79 Status final open Time Start Trip Circuit Supervision 50 HZ Measurement Error Synchronism Eeprom with default values Eeprom Error Eeprom values changed 52 a Input www.fanox.com Rev.19 296/301...
Page 297
37 Trip B 37 Trip C 37 Trip P 50BF Start 50BF Activation 50_1 Start N 50_1 Trip N 50_2 Start N 50_2 Trip N 50_1 Start A 50_1 Start B 50_1 Start C 50_1 Start P www.fanox.com Rev.19 297/301...
Page 298
In SIL-A relay, the value of the currents IL1, IL2 and IL3 have valid values, the other measures remain with value 0. Each current value is in the range 0 – 4095 where 4095 corresponds to 1,2*In e.g. a received value of 806 with a nominal value In=5A corresponds to 1,18A www.fanox.com Rev.19 298/301...
Unsolicited Retry Delay: Specifies the time to delay after an unsolicited confirm timeout before retrying the unsolicited response. Unsolicited Max. Retries: How many times should this slave resend Unsols before declaring the station offline Unsolicited Offline Retry Delay: How often to retry unsolicited responses after maxRetries attempts www.fanox.com Rev.19 299/301...