Coldroom temperature too high
1
Thermostat set too high.
2
Undersized expansion valve.
I
3
Undersized evaporator.
4
Insufficient air circulation.
UK
Suction pipes frosted
1
Excessive passage of gas through the expansion
valve or valve oversized.
2
Expansion valve locked in the open position.
L
3
The evaporator fan motor does not work.
4
High gas charge.
Discharge pipe frosted or wet
1
Drier filter restriction.
M
2
Valve on the discharge line partially closed.
•
For the drawings see pag.78-79-80-81
•
For the refrigerating diagram see pag.82
1
Adjust the setting.
2
Replace the expansion valve with one of a
suitable type
3
Replace with an evaporator with a larger
surface area
4
Improve air circulation
1
Adjust the valve or replace it with one of
the correct size.
2
Clean foreign bodies from the valve and
replace if necessary.
3
Find the cause and remove it.
4
Reduce the charge.
1
Replace the filter.
2
Open the valve or replace it if necessary.
BLOCKSYSTEM FA-FT Pag. 32
REV. 04 10/07