Plug-in insulating panel kit for FA (supplied separately)
FA 1x250 - COD.99600133
FA 1x300 - COD.99600135
FA 1x350 - COD.99600137
By adding a plug, it is possible to change the assembly method from the standard saddle
version to the plug-in version (mounting instructions will be sent together with the insulating
UK
plug-in panel).
•
Different voltage
•
Additional electronic module for master/slave operation
•
Additional electronic module for monitoring ,recording and remote management
•
Remote management system
13.
TROUBLESHOOTING
Likely cause
The compressor will not start and no humming sound
is heard
1
No power. Starter relay contacts open.
A
2
Thermal circuit breaker intervention.
3
Electrical connections loose or incorrect.
The compressor will not start (it makes a humming
sound) and the thermal circuit breaker intervenes
1
Electrical connections incorrect.
2
Low voltage at compressor.
3
Faulty start capacitor.
B
4
The relay does not close.
5
Electric motor – winding interrupted or in short
circuit.
1
2
3
4
5
6
8
Used to connect 2 Blocksystem units together in a cold room with the possibility for
synchronised operations (defrost, Blocksystem operation and temperature alarms display)
Makes it possible to connect the Blocksystem to a remote management system
Used to monitor and programme the Blocksystem from a PC or data recorder. It makes
advanced management possible (communication via modem or GSM) for all Blocksystem
alarms.
Es: FAM009Z001
230/1/50 Hz
400/3/50 Hz
110/1/60 Hz
220/3/60 Hz
220/1/60 Hz
460/3/60 Hz
230/3/50 Hz
Remedy
1
Check the line or replace the relay.
2
Check the electrical connections.
3
Tighten the connections or reconnect
wiring according to the wiring diagram.
1
Make the connections again.
2
Find and remove the cause.
3
Find the cause and replace the capacitor.
4
Find the cause and replace the relay if
necessary.
5
Replace the compressor.
BLOCKSYSTEM FA-FT Pag. 30
REV. 04 10/07