9 . B A T T E R Y
The battery is the only UPS component which is not in permanent use. It has a useful life of
approximately 3 to 5 years. However, frequent major discharges or exposure to temperatures
over 20C will shorten its life span. We therefore recommend that users recharge the battery
once every 3 months when the unit is not in use in order to compensate for natural discharging.
UPS backup time will depend on the powered load, as well as the age and condition of the
batteries.
WARNING!
Batteries should always be replaced by qualified technicians. Batteries have a very high
short circuit current: connection errors could cause electric arcs resulting in serious
burns.
1 0 . T R O U B L E S H O O T I N G
Should the UPS fail to function correctly we recommend you perform the following tests before
calling the Hot Line.

Check list:

 Is the main switch in the "ON" position?
 Is the UPS plugged into the mains power supply?
 Does the power supply fall within specified unit values?
 Has the fuse gone in the mains plug?
 Is the UPS overloaded?
 Is the battery flat or defective?
PROBLEM
No LED (or no words)
display on front panel.
Alarm continuously
sounding when mains is
normal.
In the event of power
failure, backup time is
shortened.
Mains normal but the unit
is on battery mode
1 1 . O P T I O N
Designation
Kit rack
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
8
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 02 16 AA 59 204 23
POSSIBLE CAUSE
Low battery.
Faulty battery.
UPS is not turned on.
UPS overload.
UPS overload.
Battery voltage too low.
Battery defect due to high
temperature operating
environment, or improper
use of battery.
Loose power cord.
Ref.
61429
Charge battery for up to 6 hours.
Replace with the same type of battery.
Press the power switch again to turn on
the UPS.
Check that the load matches the UPS
capability stipulated in the specifications.
Remove some non-critical load.
Charge battery up to 6 hours.
Replace with the same type of battery.
Connect the power cord properly.