GF JRGUTHERM 2T Notice De Montage Et D'utilisation page 84

Régulateur de circulation thermostatique avec robinetterie d'arrêt
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

E
Table of calibration temperatures T
Setting
[°C]
35
40
45
50
55
58 (factory setting)
60
The target value of the hot water temperature can be set with the help of adjusting screw T
The setting of the hot water temperature does not affect the disinfection temperature.
Each valve must be supplied with sufficient energy in order to enable it to regulate the heat output.
Note
To ensure control accuracy at all times, the hot water tank temperature should be set as
a closely as possible to and only slightly higher than the hot water target temperature.
84
(hot water)
1
Minimum
water temperature
water heater
[°C]
38
43
48
53
58
61
63
Maximum
water temperature
water heater
[°C]
40
45
50
55
60
63
65
.
1