Mounting The Controller - LEGRAND Wattstopper LMRC-211 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Both Room Controllers communicate to all other DLM devices connected to the DLM Local Network. Connections shown are for
example only. The low voltage LMRJ cables can connect to any DLM device with an open RJ45 receptacle.
All line voltage wiring is #12 AWG. The LMRC-211 is rated for up to 20A. The LMRC-211-347 is rated for up to 15A. Do not connect
different load types to the relay. For dimming ballasts or drivers, connect the 0-10V control wires to the 0-10V terminals that match the
load relay output connection.
Corner Mount
Sensor
Switch
The room controller mounts as the cover for a four square deep junction
box. After connecting the load and line wires, secure the LMRC-211 to the
cover tabs on a deep junction box using two screws.
J-Box
Cover a 4"x 4"x 2 1/8"deep
(minimum) box.
Plug n' Go supports the most energy efficient control strategy. For example, if one load,
one switch and one occupancy sensor are connected to the DLM local network, the system
operates the load as Manual-On, Automatic-Off.
See DLM device Quick Start Guides to determine how each device affects the PNG operation
of the LMRC-211 and the LMRC-211-347.
CONNECTIVITY
Ceiling Mount
DLM Local Network
Sensor
Low Voltage
LMRJ Cables
Dimmer
Daylight Sensor
0-10V Dimming control wires (available for each load)

MOUNTING THE CONTROLLER

Attaching LMRJ Cables
Remove rubber jack covers to use RJ45 receptacles.
Leave covers in place for all unused receptacles.
PLUG N' GO OPERATION (PNG)
Line
Earth Ground/Green wire
Voltage
Line/Hot
Black wire
Room
Controller
Neutral
White wire
Yellow wire to Load B
Deep J-Box
Red wire to Load A
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
2
Load
Examples
(any relay)
Switched
A
etc.
Switched with
0-10 Volt control
B
B
Dimming Ballast
LED Driver, etc.
0-10V Connections
Gray (-)
Violet (+)
Load A
Blue LED
ON/OFF/Dim
ON when load is
ON.
Load button:
Press & release
for ON/OFF.
Press & hold to
Dim.

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Wattstopper lmrc-211-347Wattstopper lmrc-210

Table des Matières