Settings; Advanced Settings - Komfovent C6.1 Manuel D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 70
In the "Air Quality" settings menu item, the user can set the maintained air
quality or humidity value, as well as the maintained temperature, and can de-
activate the electric heater in the unit, if necessary.

2.4.6.4. Settings

This menu item is used for the user interface basic settings. You can use it
to change the menu language, measurement units, time and the other panel
settings.

2.4.6.5. Advanced settings

Additional air handling unit settings are provided in a deeper menu screen. To
open the advanced settings window, press the "Settings" menu button for five
seconds.
Temperature control. The air handling unit has several temperature main-
tenance methods:
Supply. The unit provides the air at the user-defined temperature.
Extract. The unit automatically supplies the air at a temperature so that the
set temperature of the extract air is maintained.
Room. The unit control the ambient temperature, according to the tempera-
ture sensor in the panel.
Balance. The temperature control value of the supply air is automatically set
on the basis of the current extract air temperature, i.e. what the air will be
removed from the premises, and the same will be returned back.
Flow control. Supply and exhaust air flow control modes:
CAV – constant air flow control mode. The unit supplies and exhausts a constant air volume set by the user,
regardless of the pollution condition of the air filters and the ventilation system changes.
VAV – variable air volume control mode. The unit will supply and exhaust the air volume depending on the
ventilation needs in different rooms, i.e., the constant pressure in the system will be maintained by the vari-
able air volumes. After selecting the VAV flow control, the user will have to set the pressure maintained by
the ventilation system for each of the four modes.
UAB AMALVA we reserve the right to make changes without prior notice
C6-17-01
After selecting the "Balance" mode, the temperature setting will disappear.
When activating the air handling unit for the first time, the air flow state-
ments may differ from the real flow until the end of the air flow calibration
process. The adaptation process may take up to one hour before all the
parameters become stable.
Air quality
Air quality
800 ppm
Air humidity
80%
Air temperature
20C
Electric heater
On
Reset settings
Settings
Language
English
Flow units
m
/h
3
Screen saver
On
Panel lock
None
Touch sound
Click
Atstatyti nustatymus
Time/Date
Advanced settings
Temperature control
Flow control
Air quality control
Control sequence
Connectivity
Reset settings
31

Publicité

Table des Matières

Dépannage

loading

Ce manuel est également adapté pour:

C6.2

Table des Matières