Technical Data - S+S Regeltechnik PREMASGARD 711 VA Série Notice D'instruction

Convertisseur de pression et de pression différentielle, réglable, etalonnable, avec commutation multi-gamme et sortie active
Masquer les pouces Voir aussi pour PREMASGARD 711 VA Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

G
®
PREMASGARD
The calibratable pressure sensors PREMASGARD
V4A housing, optionally with ⁄ without display, with cable gland or M12 connector according to DIN EN 61076-2-101 and pressure port by stainless
steel quick connection (pipe fitting optional) are used to measure positive, negative or differential pressures in air. The piezoresistive measuring
element is temperature-compensated and guarantees a high degree of reliability and accuracy.
Applications of these pressure sensors are in clean room, medical and filter technology, in ventilation and air conditioning ducts, in spray booths, in
large-scale catering facilities, for filter monitoring and level measurement or for triggering frequency converters. Media measured with these
pressure transducers are air (non-precipitating), or other gaseous, non-aggressive, non-combustible media. The pressure sensor has a button for
manual zero point calibration (automatic zero point calibration optional/standard for 25 Pa) and an offset potentiometer for final value correction.
The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.

TECHNICAL DATA

Power supply:
Working resistance:
Load resistance:
Power consumption:
Measuring ranges:
Type of pressure:
Pressure port:
Medium:
Media temperature:
Accuracy:
Sum of
linearity+hysteresis:
Temp. drift values:
Zero point offset:
Positive ⁄negative pressure:
Signal filtering:
Output:
Connection type:
Electrical connection:
Cable connection:
Housing:
Housing dimensions:
Air humidity:
Protection class:
Protection type:
Standards:
Equipment:
ACCESSORIES
711x - VA
®
711x - VA (series) with eight switchable measuring ranges (eight devices in one), stainless steel
24 V AC (± 20 %); 15...36 V DC for U variant
15...36 V DC for I variant, depending on working resistance, residual ripple stabilised ± 0.3 V
R
(Ohm) = (U
-14 V) ⁄ 0.02 A for I variant, see working resistance diagram
a
b
R
> 5 kOhm for U variant
L
< 2 VA ⁄ 24 V DC, < 3.5 VA ⁄ 24 V AC
multi-range switching
with 8 switchable measuring ranges (see table)
differential pressure
equipped as standard with quick connect made from stainless steel
for PVC-fabric pressure hose Ø 6 mm (external diameter)
optionally with pipe fitting, stainless steel V2A (1.4305)
for pressure lines Ø 6 mm
clean air and non-aggressive, non-combustible gases
–20...+50 °C
Type 7112
(25 Pa): typically ± 1 Pa
Type 7110 (100 Pa): typically ± 2 Pa
Type 7111 (1000 Pa): typically ± 5 Pa
Type 7115 (5000 Pa): typically ± 25 Pa
compared to the calibrated reference device
< ± 1 % of final value
± 2 % of final value for pressure ranges < ± 250 Pa
± 0.1 % ⁄ °C
± 0.3 % ⁄ °C for pressure ranges < 250 Pa
< ± 0.7 % of final value
± 1.4 % of final value for pressure ranges < 250 Pa
max. ± 100 hPa
switchable 1 s ⁄ 10 s (via DIP switches)
0 -10 V or 4...20 mA
2- or 3-wire connection
0.14 - 1.5 mm², via plug-in screw terminal
cable gland, stainless steel V2A (1.4305)
(M 20 x 1.5; with strain relief, exchangeable,
inner diameter 6 - 12 mm) or
M12 connector (male, 5-pin, A-code)
according to DIN EN 61076-2-101
stainless steel V4A (1.4571),
with non-distortion cover bolting,
impact-resistant, high EMI shielding,
corrosion, temperature, weather- and UV-resistant
143 x 97 x 61 mm (Tyr 2E)
< 95 % r. H., non-precipitating air
III (according to EN 60 730)
IP 65 (according to EN 60 529) in the built-in state
Housing tested, TÜV SÜD, Report No. 713160960B (Skadi2)
CE conformity according to EMC Directive 2014 ⁄ 30 ⁄ EU,
according to EN 61326-1, according to EN 61326-2-3
display with illumination, three-line, cutout approx. 70 x 40 mm (W x H),
to display the ACTUAL pressure as well as the automatic zero point calibration
(see table)
10
Rev. 2021 - V13

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Premasgard 711 va lcd sériePremasgard 711 vaq sériePremasgard 711 vaq lcd sériePremasgard 711 sériePremasgard 711 va seriePremasgard 7111-u-va ... Afficher tout

Table des Matières