MCS2000-DRV2 & PSDRV2
0.5s ON/0.5s OFF
2x 0.5s ON/0.5s OFF
0.5s ON/0.5s OFF
Channel A
Channel A
Channel B
Channel B
Channel A
Channel A
Channel B
Channel B
TERMINALS MCS2000-PS and PSDRV2
~
AC input
~
AC input
Earth
Main earth, tied to housing
+24 V
2 terminal output internally connected
0V
2 terminal output internally connected, tied to housing
Page 4 of 16
Failure mode
Off
1.0s ON/0.5s OFF
Off
0.5s ON/0.5s OFF
0.5s ON/0.5s OFF
Off
2x 0.5s ON/0.5s OFF
+ 2,5s OFF
+ 2,5s OFF
0.5s ON/0.5s OFF
0.5s ON/1.5s OFF
1s ON/2.5s OFF
Warner Electric
Internal initialisation error at power ON.
Fatal error – return the drive for repair
On
•
OUTPUTS LOCKED
Short circuit or overload in operation.
•
OUTPUTS LOCKED
•
To RESET the drive you need to
power it OFF an ON again.
Internal auxiliary power supply out of
tolerances
•
OUTPUTS LOCKED
•
To RESET the drive you need to
power it OFF an ON again or when the
fault disappears
Internal auxiliary power supply failure or drive
power supply > 48 VDC +10%.
•
OUTPUTS LOCKED
•
To RESET the drive you need to
power it OFF an ON again or when the
fault disappears
Output stage temperature too high. The output
will be locked in 30s. During this time frame the
drive is in normal operation mode.
Temperature of the output stage too high.
•
OUTPUT LOCKED
•
Auto RESET when the temperature
has decreased
Ambient temperature too high. The output will
be locked in 30s. During this time frame the
drive is in normal operation mode.
Ambient temperature too high.
•
OUTPUT LOCKED
•
Auto RESET when the temperature
has decreased
(right part when facing the front of unit)
USER MANUAL
- Drive tripped
– Drive tripped.
100 to 260 VAC
auto-range
100 to 260 VAC
auto-range
24 VDC / 3,1 A
MC701r-ml-0625