S+S Regeltechnik Rymaskon 400 Modbus Notice D'instruction page 8

Module de commande d'ambiance pour l'automatisation des locaux, configurable, avec écran multifonctions et raccordement modbus
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

G
®
RYMASKON
400 - Modbus | Installation and configuration
Installation
The device is attached to the mounting frame, which is mounted onto a local dual device junction box.
The device front panel is then attached to the mounting frame by means of the upper and lower retaining clips.
Putting into operation
First, ensure that both terminal blocks are installed properly and connect them to the RYMASKON
Wait approximately 20 seconds after connecting the device.
Then press and hold the ENTER key [8] and the 6 o'clock position of the rotary pulse encoder [7] for 5 seconds
to enter the administration mode (see page 16 for a schematic diagram of the front).
The larger display shows the parameter number (e.g. "P 1") and the smaller display shows the current value.
The desired parameter is selected via the rotary encoder.
A value change is initiated by tapping the ENTER key [8] and is indicated by flashing of the current value.
Now you can use the rotary pulse encoder [7] to change the value within the permissible limits.
Tap the ENTER key [8] again to apply and save the set value.
To exit the Administrator mode, press and hold the ENTER key [8] for 2 seconds.
Configuration
The communication interface must be configured from the device (see table on page 15).
All other parameters can also be changed from the Modbus Configurator or the Modbus master.
For a full description, visit www.spluss.de
Please note
– Always ensure that the supply voltage of the individual RYMASKON
(consistent GND signal).
– When using both outputs, make sure that the valves are of the same type.
– Due to large tolerances in thermal actuators, it is not possible to adjust the valve opening precisely via a PWM signal.
– Each module address can only be assigned once.
– Only devices with addresses 1...3 can be addressed via the Modbus Configurator.
For further instructions on how to use your RYMASKON
Important notes
Our "General Terms and Conditions for Business" together with the "General Conditions for the Supply of Products and Services of the Electrical and
Electronics Industry" (ZVEI conditions) including supplementary clause "Extended Retention of Title" apply as the exclusive terms and conditions.
In addition, the following points are to be observed:
– These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!
– Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors at the device (e.g. by voltage
induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.
– This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their control authorities, the TÜV and
the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind.
– No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
– Consequential damages caused by a fault in this device are excluded from warranty or liability.
– These devices must be installed and commissioned by authorised specialists.
– The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. Deviations
from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products.
– In case of any modifications made by the user, all warranty claims are forfeited.
– This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow.
Direct sun irradiation or heat irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.
– Operating this device close to other devices that do not comply with EMC directives may influence functionality.
– This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,
or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.
– Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.
– Modifications of these records are not permitted.
– In case of a complaint, only complete devices returned in original packing will be accepted.
Notes on commissioning:
This device was calibrated, adjusted and tested under standardised conditions. When operating under deviating conditions, we recommend performing an
initial manual adjustment on-site during commissioning and subsequently at regular intervals.
Commissioning is mandatory and may only be performed by qualified personnel!
These instructions must be read before installation and commissioning and all notes provided therein are to be regarded!
®
400 devices is based on a common reference potential
®