CTP25 (30.01.2018)
Dip-Switch Setting:
Before powering unit, you must set up the Dip-Switches on the
ENABLE/DISABLE:
of the remote gas detector
affect the control unit functioning)
ON = Enabled input: the detector is installed, the measurement and the Alarms and Fault relays
are in operation. (
OFF = Disabled Input the detector is absent, the display shows Sx off. Fault relays and alarms do
not intervene. (Can also be used to exclude a faulty detector or removed for maintenance).
SW2 only used to configure the Flammable Gas Detectors
RANGE:
ON = Range 100% LIE, use only if P-type detectors (Pellistor) are installed.
OFF = Range 20% LIE, use only if K-type detectors (Catalytic) are installed
SET
ALARM: the SW2 Dip-Switches / No.2 and No.3 sets up the alarm thresholds.
No.2 and No.3 both OFF = ALARM 1 set to 10%LEL and ALARM 2 set to 20%LEL (DEFAULT SETTING).
The other alarm settings
LOGIC (of the
Relay): SW2 Dip-Switch No.4 set up the functioning mode of the ALARM 2 relay.
ON = Negative logic, the relay is de-energized, it is used for normally open valves.
OFF = Positive logic, the relay is normally energized, in case of power failure or relay failure, it automatically
moves to the alarm
position. It is used for normally closed valves
SET THE TYPE OF
sition does not affect the control unit functioning) configure each single input (SENSOR-1, SENSOR-2 and
SENSOR-3) to the type of gas to be detected, either F
See table 5.
OFF = INF
ON = TOX
The alarm thresholds for Carbon monoxide are indicated
WARNING
Configure Dip-Switches before powering the control panel.
WARNING:
,
PLEASE
SET UP THE CORRECT FULL SCALE RANGE
SETTING OF THE FULL SCALE CAN PREVENT ALARM ACTIVATION AND CONSEQUENT DANGEROUS SITUATION
). GECA
GAS
NOT LIABLE FOR DAMAGES CAUSED BY INCORRECT SELECTION
MAINTENANCE OF THE PRODUCT
The control unit after the Dip-Switch configuration does not need further adjustment after installation
During preheating of the detectors, which is of about 60 seconds, the alarm relays remain inhibited, while the Yel-
low LED and the
relay are activated.
FAULT
In case of short circuit between the connection cables to a detector, the protection circuit interrupts to it the
power supply.
Both the FAULT relay and the yellow LED will activate.
short circuit, and then turn on the unit.
If a detector is not
installed,
responding input. (SW1 Dip-Switch).
FUNCTIONAL TESTING
Periodical testing: we advise to carry out working tests every 6-12 months.
specific user's manual.
PAY ATTENTION: This procedure has to be made with extreme attention and by authorized and trained people.;
because starting this procedure it will start both Outputs (relays) causing the activation of connected alarm devices.
The TEST key is disabled if one or more inputs are more than 10% LEL (flammable gas detectors) or 35 ppm (CO
gas detectors).
Instrument operation check: Press and hold the TEST key for 5 seconds until the test procedure will start,
ed on the display. The 3 LEDs will light up and the
after 5 seconds the unit will automatically return to normal operation.
FR
DESCRIPTION
Le CTP25 est une centrale de détection de gaz et pouvant recevoir 3 sondes extérieures, qui peuvent être configu-
rés individuellement pour les gaz inflammables ou toxiques.
Pour gaz inflammables, possédant deux fond d'échelle différentes.
d'échelle de 20% LIE, s'ils sont de type catalytique (K) ou tous avec un fond d'échelle de 100% LIE, s'ils sont de
type Pellistor (P).
Pour le gaz toxique possédant
Le CTP25 est installable en saillie murale son indice de protection est IP65. L'appareil est alimenté normalement en
110÷240Vca / 50÷60Hz mais il peut être raccordé à une alimentation extérieure 24Vcc (exemple à une alimentation
secourue avec deux batteries en tampon 12V-7A/h modèle PS180/24VDC).
GECA S.r.l. - Via Enrico Fermi, 98 25064 GUSSAGO (BS) ITALY Tel. +39 030 3730218 - Fax +39 030 3730228
Istruzione / User's Manual / Manuel d'utilisation
SW1 Dip Switches No.1, No.2, No.3 enable or disable the corresponding input
(SENSOR-1, SENSOR-2 and
See Table
BY DEFAULTS ARE ALL CONFIGURED
SW2 Dip-Switch No.1
sets up the Full Scale, of the
are shown
DETECTOR:
use if Flammable Gas detectors type K or P are installed. (DEFAULT SETTING)
use only for EC type detectors (Electrochemical for CO f.s. 300ppm).
.
to prevent the automatic intervention of the FAULT relay, you
un seul fond d'échelle
SENSOR-3).
1.
ON)
in Table 4
as a function of the selected scale.
(DEFAULT SETTING).
The Dip-Switch n.1, n.2, and n.3 of SW3 (No. 4 is not used and its po-
LAMMABLE
in Table 4.
,
FOR THE INSTALLED GAS DETECTOR MODELS
,
INSTALLATION
Turn off the CTP25, remove the cause of the
FAULT, ALARM1, ALARM2 and ALARM3
Ils peuvent être configurés, tous avec un fond
de 300 ppm de monoxyde de carbone.
housing
cover board.
(No. 4 is not used and its position does not
flammable
gases.
See Table 2
(DEFAULT SETTING).
See Table
See Table 3.
(INF) or C
M
ARBON
ONOXIDE
,
CONFIGURATION OR LACK OF
must
disable
For remote detectors, refer to the
relays will be activated. Then
Pag.6/11
4.
(TOX).
. A
WRONG
(
FLAMMABLE
the cor-
indicat-