INSTALLATION
4.1 Recommended cables
Outdoor panel
Power supply unit
Using different cables between the Outdoor panel and the Power supply unit, the following
distances can be reached:
- Pair Cable (parallel) 2 x 0.75 mm² for distances up to 50 m;
- Twisted Cable 2 x 0.75 mm² for distances up to 60 m;
- Twisted Cable 2 x 1 mm² for distances up to 80 m;
For distances greater than 80 m, please request additional information from the producer.
Power supply unit
Using different cables between the Power supply unit and the Terminal, the following
distances can be reached:
- Pair Cable (parallel) 2 x 0.75 mm² for distances up to 30 m;
- Twisted Cable 2 x 0.75 mm² for distances up to 50 m;
- Twisted Cable 2 x 1 mm² for distances up to 60 m;
For distances greater than 80 m, please request additional information from the producer.
Outdoor panel
Electromagnetic lock (optional)
Pair Cable (parallel) (Cu) 2 x 0,75 mm² for distances of maximum 50 m or
pair cable (Cu) 2 x 1 mm² for distances of maximum 120 m.
Power supply unit
Flexible, copper multi-wire cable 3 x 0,75 mm²
4.2
Safety instructions for installation
è
è
è
è
è
è
Video Terminal
230 V AC network
ATTENTION! The installation, the connection to the 230V/50 Hz network and
the maintenance of the Power supply unit will only be carried out by
authorized personnel!
The installation of the Power supply unit is recommended to be made within
an electrical panel.
ATTENTION! DO NOT REMOVE THE FRONT LID! DANGER OF ELECTRIC SHOCK!
Only the protection lids of the connections can be removed.
ATTENTION! It is mandatory for the supply of the Power supply unit from the
230 V/50Hz network to be made through two automatic fuses of 10 A (on
phase and null). The connection of the F and N terminals of the Power supply
unit will be made through two isolated (Cu) wires, with a section of 0,75mm²
ATTENTION! During the installation, connection of the Power supply unit at
the 230 V/50Hz network and during service, the safety fuses from the
electrical panel must be opened. (POWER OFF)
The connection of the grounding copper wire (0,75mm²) between the
grounding hub of the electrical panel
Power supply unit
is MANDATORY.
and the grounding terminal of the