Télécharger Imprimer la page

Watts GAS SENTINEL GSX Série Mode D'emploi page 29

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Trouble shooting - alarms - faults.
Indication
Green LED lit up,
yellow LED flashing
Green LED lit up, yellow LED Gas measured with concentration
unlit, red LED flashing,
buzzer activated intermittent
Green LED lit up, yellow LED Gas alarm, concentration
unlit, red LED lit up,
buzzer activated
Green LED flashing, various
LEDs lit up or flashing
Green LED flashing, yellow
LED flashing
Master detector: green LED Alarm or malfunction in one of
Lflashing, various LEDs lit up the slaves
28
Cause
Leak detector has reached end
of its working life
over 10%LEL
over 10%LEL
Programming mode
Malfunction of the network
Solution
Leak detector is operating nor-
mally, however it should be
replaced as soon as possible
Check causes of gas leak within
30 seconds
Gas leak alarm.
See section "Behaviour in case
of alarm"
See "Programming" section"
Carry out the test procedure
from the master and make sure
that all slaves respond, check
mains cables for correct polarity
Check which slave is in alarm
status or not operating correctly.
Act accordingly.

Publicité

loading

Produits Connexes pour Watts GAS SENTINEL GSX Série

Ce manuel est également adapté pour:

Gas sentinel gsw série