Trouble shooting - alarms - faults.
Indication
No LED lit up
All LEDs flashing in rotation Leak detector in warm-up phase
Green LED lit up,
all others unlit
Green LED lit up,
yellow LED lit up
Cause
No power supply, leak detector
not powered
Normal operation
Fault found in the electronic
circuit or sensor
Solution
Make sure of the power supply
to the home
Make sure that the electrical con-
nection has been made accor-
ding to the wiring diagram, make
sure that the electrical power
supply reaches the terminals.
If the problem persists, call the
technical service (the leak detec-
tor is not provided with fuses, do
not break the safety seal)
Wait for 2.5 minutes until the end
of the automatic warm-up proce-
dure
Leak detector is in normal
operation
In the case of installation in
network of two or more sensors,
the fault of a slave is given on the
master: if the fault is on a slave,
the master has the green LED
flashing, check the slave and not
the master. Send the faulty detec-
tor to technical service department
27