Air-Conditioners
PEA-A12, 18AA4
INSTALLATION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner
unit.
MANUEL D'INSTALLATION
Veuillez lire le manuel d'installation en entier avant d'installer ce climatiseur pour éviter tout accident et vous
assurer d'une utilisation correcte.
FOR INSTALLER
POUR L'INSTALLATEUR
English
Français

Publicité

Chapitres

Table des Matières
loading

Sommaire des Matières pour Mitsubishi Electric Mr.SLIM PEA-A12AA4

  • Page 1 Air-Conditioners PEA-A12, 18AA4 INSTALLATION MANUAL FOR INSTALLER English For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit. MANUEL D’INSTALLATION POUR L’INSTALLATEUR Français Veuillez lire le manuel d’installation en entier avant d’installer ce climatiseur pour éviter tout accident et vous assurer d’une utilisation correcte.
  • Page 2 [Fig. 3-1] (Unit: mm [in]) 50 ~ 150 [1-31/32 ~ 5-29/32] 450 [17-23/32] [29/32] [3-9/16] 57 [2-1/4] 20 [13/16] A Access door 1 600 mm [23-5/8 in] or more B Electrical parts box 2 100 mm [3-15/16 in] or more C Air inlet 3 10 mm [13/32 in] or more D Air outlet...
  • Page 3 [Fig. 5-1] [Fig. 5-2] [Fig. 5-3] C Nuts (field supply) A Unit body D Washers (accessory) B Lifting machine A Indoor unit’s bottom surface E M10 hanging bolt (field supply) [Fig. 6-1] (Unit: mm [in]) øB øA Model PEA-A12AA4 12.7 [1/2] 6.35 [1/4] 6.35 [1/4] PEA-A18AA4...
  • Page 4 [Fig. 6-10] Max. 20m [65 ft] 1.5-2 m [5 to 7 ft] Max. 300 mm [11-13/16 in] Correct piping Wrong piping A Insulation (9 mm [3/8 in] or more) B Downward slope (Drain pipes should have an inclination of 1/100 or more.) C Support metal K Air bleeder L Raised...
  • Page 5 [Fig. 7-1] A Air inlet B Air outlet C Access door D Ceiling surface E Canvas duct F Air filter G Inlet grille [Fig. 8-1] A Indoor unit B Outdoor unit C Wired remote controller D Main switch/fuse CN105 E Grounding F Indoor controller board G Radio frequency interface for RF thermostat For Power supply...
  • Page 6 [Fig. 8-3] A Indoor terminal block A Indoor terminal block 4 Always install an earth wire (1-core 1.5 mm B Ground wire (green/yellow) B Ground wire (green/yellow) [AWG 16]) longer than other cables C Indoor/outdoor unit connecting cable 3- 5 Wired remote controller cable core 1.5 mm [AWG 16] or more Wire No ×...
  • Page 7 11.1 [Fig. 11-1] H Refrigerant gas cylinder for R410A with A Indoor unit siphon B Union I Refrigerant (liquid) C Liquid pipe J Electronic scale for refrigerant charging D Gas pipe K Charge hose (for R410A) E Stop valve L Gauge manifold valve (for R410A) F Outdoor unit M Service port G Refrigerant gas cylinder operating valve...
  • Page 8: Table Des Matières

    Contents 1. Safety precautions ................... 8 9. Test run ....................14 2. Selecting the installation location ............. 8 10. Easy maintenance function ..............16 3. Selecting an installation site & Accessories ..........9 11. Maintenance ..................16 4. Fixing hanging bolts ................. 9 5.
  • Page 9: Selecting An Installation Site & Accessories

    3. Selecting an installation site & Accessories • Select a site with sturdy fixed surface sufficiently durable against the weight of unit. Warning: • Before installing unit, the routing to carry in unit to the installation site should be The unit must be securely installed on a structure that can sustain its weight. If determined.
  • Page 10: Refrigerant Piping Work

    6. Refrigerant piping work 6.1. Refrigerant pipe 6.2.3. Putting nut on [Fig. 6-5] (P.3) [Fig. 6-1] (P.3) a Flare nut a Indoor unit b Copper tube b Outdoor unit • Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube Refer to the Instruction Manual that came with the outdoor unit for the restrictions on having completed burr removal.
  • Page 11: Purging Procedures Leak Test

    6. Refrigerant piping work Refrigerant pipe insulation • After connecting refrigerant piping, insulate the joints (flared joints) with thermal Remove the gage manifold valve quickly from the service port of the stop valve. insulation tubing as shown below. After refrigerant pipes are connected and evacuated, fully open all stop valves on [Fig.
  • Page 12: Confirming Drain Discharge

    6. Refrigerant piping work 6.6. Confirming drain discharge [Drainage by gravity] 1. Insert the drain hose (accessory) into the drain port. s s s s s Make sure that the drain-up mechanism operates normally for discharge (The drain hose must not be bent more than 45° to prevent the hose from breaking and that there is no water leakage from the connections.
  • Page 13: Remote Controller

    8. Electrical work 2 Use the C button to set the refrigerant address (3) to 00. [Fig. 8-2-3] (P.5) 3 Press D and [--] will start to flash in the unit number (4) display. A Use conduit to keep the weight of the cable and external force from being applied to the 4 Use the C button to set the unit number (4) to 01-04 or AL.
  • Page 14: Test Run

    8. Electrical work Function table 1 Select unit number 00 Mode Settings Mode no. Setting no. Initial setting Check Power failure automatic recovery*1 Not available (AUTO RESTART FUNCTION) Available *1 Indoor temperature detecting Indoor unit operating average Set by indoor unit’s remote controller Remote controller’s internal sensor LOSSNAY connectivity Not Supported...
  • Page 15: Auto Restart Function

    9. Test run [Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.) Wired remote controller IR wireless remote controller RF thermostat Symptom Remark Beeper sounds/OPERATION INDICATOR lamp flashes Check code (Number of times) Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit) Compressor overcurrent interruption U3, U4 Open/short of outdoor unit thermistors...
  • Page 16: Easy Maintenance Function

    10.Easy maintenance function (For wired remote controller only) Display example (Comp discharge temperature 147°F) By using the maintenance mode, you can display many types of maintenance data on the wired remote controller such as the heat exchanger temperature and com- pressor current consumption for the indoor and outdoor units.
  • Page 17: Consignes De Sécurité

    Index 1. Consignes de sécurité ................17 9. Marche d’essai ..................24 2. Choisir l’emplacement de l’installation ........... 17 10. Fonction d’entretien aisé ................ 26 3. Sélection de l’emplacement d’installation et accessoires ...... 18 11. Entretien ....................26 4. Fixation des boulons de suspension ............18 5.
  • Page 18: Sélection De L'emplacement D'installation Et Accessoires

    2. Choisir l’emplacement de l’installation Attention: • Emplacement où il existe une grande quantité d’huile de machine. Les emplacements sousmentionnés doivent être évités pour effectuer l’instal- • Sites salins. lation s’il existe un risque de panne pour le climatiseur. • Stations thermales. •...
  • Page 19: Installation De L'appareil

    5. Installation de l’appareil 5.1. Suspension de l’appareil 5.2. Assurer l’emplacement de l’appareil et fixer les s s s s s Apporter l’appareil intérieur emballé sur le lieu de son installation. boulons de suspension s s s s s Pour le suspendre, utiliser une poulie de levage pour le soulever et le faire s s s s s Utiliser le calibre livré...
  • Page 20: Connexion Des Tuyaux

    6. Mise en place des tuyaux de réfrigérant 6.3. Connexion des tuyaux Utiliser la pompe à vide. [Fig. 6-8] (P.3) (Vider pendant plus de 15 minutes.) • Appliquer une fine couche d’huile de réfrigérant sur la surface du siège de con- duite.
  • Page 21: Confirmation Des Décharges D'écoulement

    6. Mise en place des tuyaux de réfrigérant 6.6. Confirmation des décharges d’écoulement Tuyaux groupés D D. E. ø 32 mm [1-1/4 in] TUBE PVC s s s s s Veiller à ce que le mécanisme de décharge d’écoulement fonctionne nor- E Elargir le plus possible.
  • Page 22: Installations Électriques

    8. Installations électriques 8.1. Alimentation électrique [Fig. 8-2-4] (P.5) A Bloc terminal pour la connexion de l’appareil intérieur/extérieur Spécification électrique Capacité de disjoncteur (A) B Bornier de la télécommande filaire Alimentation électrique PEA-A12AA4 PEA-A18AA4 C Câble de connexion de l’appareil intérieur/extérieur (1 phase ~/N, 208/230V, 60Hz) D Télécommande à...
  • Page 23: Réglage Des Fonctions

    8. Installations électriques 8.4. Réglage des fonctions 3) Pour télécommande sans fil infrarouge [Fig. 8-6] (P.6) 1. Modification des réglages de pression statique externe. 8.4.1 Réglage des fonctions sur l’appareil (Sélection des fonctions • Veillez à changer le réglage de la pression statique extérieure selon le conduit et la de l’appareil) grille utilisés.
  • Page 24: Marche D'essai

    9. Marche d’essai 9.1. Avant la marche d’essai • La résistance de l’isolation chute en raison de l’accumulation de réfrigérant dans le compresseur. La résistance dépassera 1 MΩ après que le compres- s Lorsque l’installation, le tuyautage et le câblage des appareils intérieur et seur a chauffé...
  • Page 25: Fonction De Redemarrage Automatique

    9. Marche d’essai • Sur la télécommande sans fil infrarouge La sonnerie continue de la section de réception de l’appareil intérieur retentit. Clignotement du témoin de fonctionnement • Sur la télécommande sans fil Code de vérification affiché sur l’afficheur LCD. •...
  • Page 26: Fonction D'entretien Aisé

    10.Fonction d’entretien aisé (uniquement pour la télécommande à fil) Exemple d’affichage (température de décharge du comp. 147 °F) Le mode d’entretien permet d’afficher de nombreux types de données d’entretien sur la télécommande à fil, comme la température de l’échangeur de chaleur et la consommation actuelle du compresseur pour les appareils intérieur et extérieur.
  • Page 28 This product is designed and intended for use in the residential, commercial and light-industrial environment. Please be sure to put the contact address/telephone number on this manual before handing it to the customer. HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN KB79U390H01...

Ce manuel est également adapté pour:

Mr.slim pea-a18aa4