The table below will show you the different causes of inverter stopping.
CAUSE
Low
battery
voltage Voltage <
0.87*Unom
Deep
discharged
battery 0.75*Unom
Overheating
Battery
overvoltage
1.33*Unom
Short circuit at the
ouptut
Overload
Battery
reverse
polarity
B
L
O
ATTERY
IFETIME
Cycling a battery in permanent charging
mode from 0 to 30% is often a cause of early
aging of batteries, particularly in solar home
systems.
In order to enhance the battery lifetime, the
AJ inverters are equipped with a unique
function that will readjust the low voltage
disconnection (LVD) threshold according to
the behavior of the user consumption. This
allows a full recharge of the battery.
This function can be activated at anytime as
per the procedure described p. 8.
An indicator (green LED 2) only available on
from AJ 275-12 to 700-48 is lit or blinks when this
function is activated. The number of blinkings
indicates the LVD currently applied.
User Manual
CONSEQUENCE
Inverter
temporary
stopped,
the
indicator blinks.
Inverter stopped
Inverter
temporary
stopped,
the
indicator blinks.
Inverter stopped.
Inverter stopped.
Inverter stopped.
Internal
fuse
down.
– BLO
PTIMIZER
SOLUTION
Automatic
green
voltage rises at 1.04*Unom.
The inverter should be manually restarted
Inverter should be manually restarted
when
the
=0.87*Unom
Automatic restart when the temperature
green
reaches the normal range.
Wait until the battery voltage reaches the
correct level.
Push the ON/OFF button to reactivate the
inverter. 1.25*Unom
Eliminate the short circuit.
Push the ON/OFF button to reactivate the
inverter.
Use the inverter only in the range of its
nominal power. Regular use in overload
power diminishes the lifetime of the
inverter.
Push the ON/OFF button to reactivate the
inverter.
broken
Back to manufacturer for testing.
If this indicator is lit continuously, this means
that the use of the battery is correct and that
it was well charged. The LVD is then set at
0.87*unom (10.5, 21or 42V) as per the model.
This also means that you have the widest
availability of the energy stored and that your
battery is likely to last longer.
If the indicator is blinking one or several times,
this means that the use of the battery is
restricted and that the disconnection voltage
was set according to the table below (+/- 2%).
AJ V2.6
restart
when
the
battery
has
AJ
battery
reached
9/46