2.4 Electrical Connections
The electrical connection must only be carried through by qualified personnel.
Follow the respective national safety standards (e. g. VDE 0100) for mounting,
start-up and operation.
All actions must only be carried through without voltage connected.
Disregarding the corresponding standard may cause heavy injuries and/or property
damage.
Shielded cables are recommended for the electrical connection. An additionally required voltage
supply should be connected through a separate second cable. After opening the positioner
cover the screw terminals of the connecting block (1) can be accessed.
The maximum connector size is 1.5 mm²
Cable bushings which are not used should be sealed in any case using a suitable
sealing cap to preserve the protection class (IP65).
The positioner has to be earthed. An earthing screw is located on the outside of the
casing and on the PCB near the connection terminals.Also, shielded cables must be
used.
25
1
screw terminals
2
key "IN"
3
key "OUT"
4
LED red
5
LED green
6
Function end / shield
7
interface connection
8
plug terminal for additional modules