Scheduled arm and disarm
zones settings
Syntax:
【58 】
+【group number 01~04】
+【 00-99 Defense zone
begin the area code】
+ 【 00-99 Defense zone
ends area code】
+ 【#】
Set the type of defense zone
Syntax:
【60】
+ 【00-99 zone number】
+ 【1-8 type】
+ 【0/1】
+ 【#】
Set mode of wired alarm
zone
Syntax:
【61】
+ 【zone number 51-54】
+ 【0/1】
+ 【#】
Used to set when the four group of zone to be controlled by scheduled arm and
disarm
Example: To set up the first group scheduled arm and disarm control 00-50
defense zone.
Method one:
press # enter the setup status and press 58010050#, press * then press # exit
Setup
Method two:
after calling and connected to the panel from remote, press 58010050#
Method three:
Send SMS message 123458010050#
To set 99 zone type, 00-99 represents 0-99 zone number,
1-8 represents one of the 8 zone type:
1.
norMal
2.
STAY ARM
3.
intelligent
4.
EMERGENCY
5.
cloSed
6.
cHiMe
7.
WelcoMe
8.
Help Senior
The last 0/1 represents 0 siren of panel produce no sound upon alarming while
1 is sounded.
Example: Set zone number 2 as STAY zone type, and siren not sound upon
alarming2.
Method one:
Press # enter the configuration mode, press 600220#, press * then press # To exit
Setup.
Method two:
after calling and connected to the panel from remote, press 600220#
Method three:
Send SMS message 1234600220#
Set wired alarm zone to NO or NC. The zone number of 51-54 are wired defense
zones, system default is 51-54 are wired zones with NO mode.
0 means no and 1 means nc
no means short-circuit to alarm
nc means open-circuit to alarm
example: Set 51 zone to nc,
Method one:
# Key enters the configuration mode, press 61511#
* then press # to exit Setup.
Method two:
after calling and connected to the panel from remote, press 61511#
Method three:
Send SMS message 123461511#
remark: on the back pane of the alarm panel
51 = zone 1 and labelled Z1
52 = zone 2 and labelled Z2
53 = zone 3 and labelled Z3
54 = zone 4 and labelled Z4
EN ::: 35