7.5 Additional prescriptions for safety applications with operator protection
functions
Provided that all previous requirements for the devices are fulfilled, for installations
with operator protection function additional requirements must be observed.
- The utilization implies knowledge of and compliance with following standards:
EN ISO 13849-1, EN IEC 62061, EN 60204-1, EN ISO 12100.
- In the risk analysis, take into account that in manual start mode a possible sticking of
the start button can lead to an immediate activation of the module.
- If expansion modules or external contactors are used, make sure that they have
forcibly guided contacts and connect in feedback an NC contact of each device.
7.6 Limits of use
- Use the device following the instructions, complying with its operation limits and the
standards in force.
- The devices have specific application limits (min. and max. ambient temperature,
maximum currents, IP protection degree, etc.) These limitations are met by the device
only if considered individually and not as combined with each other.
- According to EU directives, this device is not intended for private use.
- The manufacturer's liability is to be excluded in the following cases:
1) Use not conforming to the intended purpose.
2) Failure to adhere to these instructions or regulations in force.
3) Fitting operations not carried out by qualified and authorized personnel.
4) Omission of functional tests.
- For the cases listed below, before proceeding with the installation contact our as-
sistance service (see paragraph SUPPORT):
a) In nuclear power stations, trains, airplanes, cars, incinerators, medical devices or
any application where the safety of two or more persons depend on the correct opera-
tion of the device.
b) Applications not contemplated in this instruction manual.
8 MARKINGS
The outside of the device is provided with external marking positioned in a visible
place. Marking includes:
- Producer trademark
- Product code
- Batch number and date of manufacture. Example: CS1-123456 (A19). The last part
of the production batch refers to the month of manufacture (A = January, B = February,
etc.) as well as the year of manufacture (19 = 2019, 20 = 2020, etc.).
9 TECHNICAL DATA
9.1 Housing
Material: Polyamide PA 66, self-extinguishing V0 acc. to UL 94
Protection degree:
Cable cross section:
Terminal tightening torque:
9.2 General data
SIL:
Performance Level (PL):
Safety category:
MTTF
:
D
DC:
PFH
:
D
Mission time:
Ambient temperature:
Storage temperature:
Mechanical endurance:
Electrical endurance:
Pollution degree:
Impulse withstand voltage U
:
imp
Rated insulation voltage U
:
i
Overvoltage category:
Air and surface distances:
9.3 Power supply
Rated supply voltage U
:
n
Supply voltage tolerance:
Max. DC residual ripple in DC:
Power consumption AC:
Power consumption DC:
9.4 Control circuit
Protection against short circuits:
PTC times:
Maximum resistance per input:
Current per input:
Min. duration of start impulse t
:
MIN
Response time t
:
A
Release time t
:
R1
Release time
in absence of power supply t
:
R
Simultaneity time t
:
C
9.5 Output circuit
Output contacts:
Contact type:
Material of the contacts:
Maximum switching voltage:
Max. current per contact:
Conventional free air thermal current I
Max. total current Σ I
:
2
th
IP40 (housing), IP20 (terminal strip)
0.2 ... 2.5 mm
(24 ... 12 AWG)
2
0.5 ... 0.6 Nm
Up to "Maximum SIL 3" acc. to
EN IEC 62061:2021
Up to PL e acc. to EN ISO 13849-1:2015
Up to cat. 4 acc. to EN ISO 13849-1:2015
152 years
High
1.84 E-10
20 years
-25°C ... +55°C
-25°C ... +70°C
> 10 million operating cycles
> 100,000 operating cycles
external 3, internal 2
4 kV
250 V
II
acc. to EN 60947-1
24 Vac/dc; 50...60 Hz
(articles CS AR-04•024)
120 Vac; 50...60 Hz
(articles CS AR-04•120)
230 Vac; 50...60 Hz
(articles CS AR-04•230)
±15% of U
n
10%
< 5 VA
< 2 W
PTC resistance, Ih = 0.5 A
Response time > 100 ms, release time > 3 s
≤ 50 Ω
< 30 mA
> 100 ms
< 50 ms
< 20 ms
< 70 ms
unlimited
3 NO safety contacts
1 NC auxiliary contact
forcibly guided
gold-plated silver alloy
230/240 Vac; 300 Vdc
6 A
: 6 A
th
64 A
2
Minimum current:
Contact resistance:
External protection fuse:
Maximum switching load:
Utilization categories acc. to EN 60947-5-1:
AC-15 (50 ... 60 Hz)
DC-13 (6 op. cycles/minute)
Utilization category acc. to UL 508:
9.6 Compliance with standards
EN 60204-1, EN ISO 13855, EN ISO 14118, EN ISO 12100, EN ISO 13850, EN 60529,
EN 61000-6-2, EN 61000-6-3, EN 61326-1, EN 60664-1, EN 60947-1, EN IEC 63000,
EN ISO 13849-1, EN ISO 13849-2, EN IEC 62061, UL 508, CSA C22.2 n° 14,
GB/T14048.5-2017
9.7 Compliance with directives
Machinery Directive 2006/42/EC, EMC Directive 2014/30/EU, RoHS Directive
2011/65/EU.
10 SPECIAL VERSIONS ON REQUEST
Special versions of the device are available on request.
These special versions may differ substantially from the indications in these operating
instructions.
The installer must ensure that he has received written information regarding the use
of the special version requested (see paragraph SUPPORT).
11 DISPOSAL
At the end of service life product must be disposed of properly, according to the
rules in force in the country in which the disposal takes place.
12 SUPPORT
The device can be used for safeguarding people's physical safety, therefore in case of
any doubt concerning installation or operation methods, always contact our technical
support service:
Pizzato Elettrica Srl
Via Torino, 1 - 36063 Marostica (VI) - ITALY
Telephone +39.0424.470.930
E-mail tech@pizzato.com
www.pizzato.com
Our support service provides assistance in Italian and English.
13 EC CONFORMITY DECLARATION
I, the undersigned, as a representative of the following manufacturer:
Pizzato Elettrica Srl - Via Torino, 1 - 36063 Marostica (VI) – ITALY
hereby declare that the product is in conformity with whatever prescribed by the
2006/42/EC Machine Directive. The complete version of the present conformity
declaration is available on our website www.pizzato.com
Marco Pizzato
DISCLAIMER:
Subject to modifications without prior notice and errors excepted. The data given in this sheet
are accurately checked and refer to typical mass production values. The device descriptions and
its applications, the fields of application, the external control details, as well as information on
installation and operation, are provided to the best of our knowledge. This does not in any way mean
that the characteristics described may entail legal liabilities extending beyond the "General Terms
of Sale", as stated in the Pizzato Elettrica general catalogue. Customers/users are not absolved
from the obligation to read and understand our information and recommendations and pertinent
technical standards, before using the products for their own purposes. Taking into account the great
variety of applications and possible connections of the device, the examples and diagrams given in
the present manual are to be considered as merely descriptive; the user is deemed responsible for
checking that the specific application of the device complies with current standards. This document
is a translation of the original instructions. In case of discrepancy between the present sheet and
the original copy, the Italian version shall prevail. All rights to the contents of this publication are
reserved in accordance with current legislation on the protection of intellectual property. The
reproduction, publication, distribution and modification, total or partial, of all or part of the original
material contained therein (including, but not limited to, texts, images, graphics), whether on paper
or in electronic form, are expressly prohibited without written permission from Pizzato Elettrica Srl.
All rights reserved. © 2023 Copyright Pizzato Elettrica
6/18
10 mA
≤ 100 mΩ
4 A
1380 VA/W
U
= 230 V, I
= 3 A
e
e
U
= 24 V, I
= 4 A
e
e
C300