2. Installation location
Fig. 2-5
Fig. 2-9
Fig. 2-12
Fig. 2-15
2.5.2. When installing a single outdoor unit
en
Minimum dimensions are as follows, except for Max., meaning Maximum dimen-
sions, indicated.
Refer to the figures for each case.
Obstacles at rear (Fig. 2-5)
Obstacles at rear and above (Fig. 2-6)
Obstacles at rear and sides (Fig. 2-7)
Obstacles at front (Fig. 2-8)
* When using the optional air outlet guides, the clearance is 20" (500 mm) or more.
Obstacles at front and rear (Fig. 2-9)
* When using the optional air outlet guides, the clearance is 20" (500 mm) or more.
Obstacles at rear, sides, and above (Fig. 2-10)
• Do not install the optional air outlet guides for upward airflow.
5
Fig. 2-6
Fig. 2-10
Fig. 2-13
Fig. 2-16
2.5.3. When installing multiple outdoor units
Leave 1" (25 mm) space or more between the units.
• Do not install the optional air outlet guides for upward airflow.
* When using the optional air outlet guides installed for upward airflow, the clearance is
* When using the optional air outlet guides installed for upward airflow, the clearance is
Fig. 2-7
Obstacles at rear (Fig. 2-11)
Obstacles at rear and above (Fig. 2-12)
• No more than 3 units must be installed side by side. In addition, leave space as shown.
Obstacles at front (Fig. 2-13)
* When using the optional air outlet guides, the clearance is 40" (1000 mm) or more.
Obstacles at front and rear (Fig. 2-14)
* When using the optional air outlet guides, the clearance is 40" (1000 mm) or more.
Single parallel unit arrangement (Fig. 2-15)
40" (1000 mm) or more.
Multiple parallel unit arrangement (Fig. 2-16)
60" (1500 mm) or more.
Stacked unit arrangement (Fig. 2-17)
• The units can be stacked up to 2 units high.
• No more than 2 stacked units must be installed side by side. In addition, leave space as
shown.
in (mm)
Fig. 2-8
Fig. 2-11
Fig. 2-14
Fig. 2-17