1.19 ADVANCED MENU TABLE OF PARAMETERS

PARAM.
P.11
P.12
P.13
P.14
P.15
P.16
P.17
P.18
P.19
P.20
Capacitor overload alarm threshold (%)
Overload threshold for immediate
P.21
P.22
Overload event counter clearing time (h)
P.23
Overload alarm reset time (min)
P.24
Unit of measure for temperature
P.25
P.26
P.27
Temperature alarm threshold (° C)

1.20 DESCRIPTION OF ADVANCED MENU PARAMETERS

P.11 - Type of connection
Programs either single-phase or three-phase connection.
P.12 - CT connection recognition
When set to Automatic, the controller operates in 2 quadrants and at power on, it recog-
nizes direction of current flow in the C.T.
When set to Direct, the controller operates in 4 quadrants and can be used both in normal
or co-generation systems. It is however necessary to check the correct CT connection by
making sure the decimal point of the cosϕ measurement is not flashing with energy import
FUNCTION
Type of connection
CT connection recognition
Frequency recognition
Step power adjustment
Regulation mode
Step connection mode
Co-generation cosϕ set-point
Disconnection sensitivity
Step disconnection at
change to MANU mode
step disconnection (%)
Fan start temperature (° C)
Fan stop temperature (° C)
3PH Three phase
1PH Single phase
Aut Automatic
rEU Inverse
Aut Automatic
On Enabled
OFF Disabled
Std Standard
Std Standard
0.80 Ind ... 0.80 Cap
1 ... 600sec
OFF Disabled
On Enabled
0 ... 150 %
0 ... 200 %
1 ... 30min
° C ° Celsius
° F ° Fahrenheit
0 ... 100 ° C
32 ... 212 ° F
0 ... 100 ° C
32 ... 212 ° F
50 ... 100 ° C
122 ... 212 ° F
36
RANGE
DEFAULT
dir Direct
50H 50Hz
60H 60Hz
Bnd Band
Lin Linear
OFF
OFF
OFF
OFF
1 ... 240h
3PH
Aut
Aut
OFF
Std
Std
OFF
OFF
OFF
25
50
24
5
° C
55
50
60