V8043 Zone Valves
with Press Connection
Model
Pipe Size
V8043A1311/U
DN15
V8043A1312/U
DN20
V8043A1612/U
DN20
V8043A1313/U
DN25
V8043E1411/U
DN15
V8043E1412/U
DN20
V8043E1712/U
DN20
V8043E1413/U
DN25
V8043F1511/U
DN15
V8043F1512/U
DN20
V8043F1812/U
DN20
V8043F1513/U
DN25
APPLICATION
These valves consist of an actuator motor and valve
assembly for controlling the flow of hot and/or cold
water. The V8043A provides two-position, straight-
through control of supply water. The valves are
designed for use with fan coil and other units
requiring quiet, compact water valves. The V8043E
and V8043F also control supply water for baseboard
radiators and convectors.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to
follow them could damage the product or cause
a hazardous condition.
2. Check the ratings given in the instructions and
on the product to make sure the product is
suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
1/2" Zone Valve Pro Press with 18" lead wires
3/4" Zone Valve Pro Press with 18" lead wires
3/4" Zone Valve Pro Press with 18" lead wires
1" Zone Valve Pro Press with 18" lead wires
1/2" Zone Valve Pro Press with 18" lead wires and End Switch
3/4" Zone Valve Pro Press with 18" lead wires and End Switch
3/4" Zone Valve Pro Press with 18" lead wires and End Switch
1" Zone Valve Pro Press with 18" lead wires and End Switch
1/2" Zone Valve Pro Press with Terminal Block Connections and End Switch
3/4" Zone Valve Pro Press with Terminal Block Connections and End Switch
3/4" Zone Valve Pro Press with Terminal Block Connections and End Switch
1" Zone Valve Pro Press with Terminal Block Connections and End Switch
INSTALLATION INSTRUCTIONS
Description
CAUTION
1. Disconnect power supply before connecting
wiring to prevent electrical shock of
equipment damage.
2. Normally it is not necessary to remove the
powerhead from the valve body during
installation. If the valve must be disassembled,
be certain that it is reassembled with the water
flow in the direction of the arrow. Reversal of
the powerhead will result in damage to the
gear train.
3. On 24V systems, never jumper the valve coil
terminals even temporarily. This may burn
out the heat anticipator in the thermostat.
IMPORTANT
Use this valve in hydronic heating systems
which do not contain dissolved oxygen in the
system water. The dissolved oxygen, which is
found in systems that have a frequent source
of makeup water, causes the rubber plug inside
the valve to deteriorate and eventually fail.
LOCATION
Install the valve in an area with adequate clearance to:
—
move the manual opening lever on the side of
the powerhead;
—
remove the powerhead cover;
—
wire the powerhead;
—
replace the powerhead motor.
Max ΔP (psi)
C
v
20
3
20
3.5
8
8
6.5
8.5
20
3
20
3.5
8
8
6.5
8.5
20
3
20
3.5
8
8
6.5
8.5