20. Set the control console back into place on the cooktop. For
a proper fit, the flange of the control console must hook over
the lip on the front of the cooktop.
A
B
A. Control console flange
B. Front lip of range cooktop
21. Check that the control console is flush with the top edge of
the cooktop.
A
A. Flush with top of cooktop
22. Replace the 2 screws on each side of the control console.
23. Push the cooktop back into place in the cutout.
24. Replace the control knobs.
25. Replace burner grates.
26. Plug in cooktop or reconnect power.
27. Test the flame by turning the control from LO to HI, checking
the flame at each setting.
Complete Installation
1. Refer to the "Make Gas Connection" section for properly
connecting the cooktop to the gas supply.
2. Refer to the "Electronic Ignition System" section for proper
burner ignition, operation, and burner flame adjustments.
IMPORTANT: You may have to adjust the LO setting for each
cooktop burner.
Checking for proper cooktop burner flame is very important.
The small inner cone should have a very distinct blue flame
/
" (0.64 cm) to
/
" (1.3 cm) long. The outer cone is not
1
1
4
2
as distinct as the inner cone. LP gas flames have a slightly
yellow tip.
3. Refer to "Complete Installation" in the "Installation
Instructions" section of this manual to complete this
procedure.
14
Natural Gas Conversion
1. Turn the manual shut-off valve to the closed position.
A
A. To cooktop
B. Shut-off valve (closed position)
C. Gas supply line
2. Unplug cooktop or disconnect power.
To Convert Gas Pressure Regulator
1. Remove the access cap by using a wrench, turning the
access cap counterclockwise.
2. Remove spring retainer from the cap by pushing against the
flat side of the spring retainer. Look at the spring retainer to
locate the "LP" or "NAT" position. Turn over the spring
retainer so the "NAT" is showing on the bottom. Snap the
spring retainer back into the cap. Reinstall the cap onto the
regulator.
E
D
A. Access cap
B. Gasket
C. Gas pressure regulator
3. Test the gas pressure regulator and gas supply line.
The regulator must be checked at a minimum 1" (2.5 cm)
water column above the set pressure. The inlet pressure
to the regulator should be as follows for operation and
checking the regulator setting:
LP Gas:
Minimum pressure 6" (15.2 cm) WCP
Maximum pressure 14" (35.5 cm) WCP
Gas Supply Pressure Testing
Gas supply pressure for testing regulator must be at least
1" water column pressure above the manifold pressure
shown on the model/serial/rating plate.
Line pressure testing above
The cooktop and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of
/
psi (3.5 kPa).
1
2
Line pressure testing at
The cooktop must be isolated from the gas supply piping
system by closing its individual manual shut-off valve during
any pressure testing of the gas supply piping system at test
pressures equal to or less than
B
C
A
B
C
D. NAT position
E. LP position
/
psi gauge (14" WCP)
1
2
/
psi gauge (14" WCP) or lower
1
2
/
psi (3.5 kPa).
1
2