Télécharger Imprimer la page

Publicité

Liens rapides

H-6508
HARD-WIRED EXIT SIGN
TOOLS NEEDED
Flathead Screwdriver
CAUTION! When using electrical equipment,
basic safety precautions should always be
followed, including the following:
• Do not use outdoors.
• Do not mount near gas or electric heaters.
• Do not let power cords touch hot surfaces.
• Use caution when servicing batteries. Avoid
possible shorting.
• Equipment should be mounted in locations
and at heights where it will not readily be
subjected to tampering by unauthorized
personnel.
BACK MOUNTING
1.
Drill 1/4" holes into oblong knock-outs on back plate
that correspond to junction box holes to be used.
(See Figure 1)
Figure 1
Wire Nuts
EXIT Panel
PAGE 1 OF 6
1 800 295-5510
uline.ca
Phillips Screwdriver
INSTALLATION
Junction
Box
Back Plate
Plastic
Housing
Diffuser
Snap-in
Directional Arrow
SAFETY
• The use of accessories not recommended
by the manufacturer may cause an unsafe
condition.
• Do not use this equipment for anything other
than intended use.
• Before wiring to AC service, turn off AC power
at fuse or circuit breaker.
• Disconnect AC power and unplug battery
before servicing.
• Only use specified lamps in the fixture.
• Battery in this unit may not be fully charged.
After the AC service is supplied to the unit, let
the battery charge for at least 24 hours before
performing any tests.
2. Feed the transformer input leads through center
hole and make the proper connections. If using
120VAC, connect the black and white leads to the
building utility. If using 347VAC, connect the red and
white leads to the building utility. Cap off unused
wire. If the unit is self-powered, ensure battery
connector snaps together.
3. Feed excess wire into junction box and secure back
plate to junction box. (See Figure 1)
4. Snap in arrows on EXIT panel as required. Then snap
EXIT panel to housing: top first, then bottom.
(See Figure 1)
NOTE: Use flexible
conduit only.
(See Figure 2)
Para Español, vea páginas 3-4.
Pour le français, consulter la pages 5-6.
Figure 2
0624 IH-6508

Publicité

loading

Sommaire des Matières pour Uline H-6508

  • Page 1 Para Español, vea páginas 3-4. Pour le français, consulter la pages 5-6. H-6508 1 800 295-5510 uline.ca HARD-WIRED EXIT SIGN TOOLS NEEDED Flathead Screwdriver Phillips Screwdriver SAFETY CAUTION! When using electrical equipment, • The use of accessories not recommended basic safety precautions should always be...
  • Page 2 (See Figure 7) Battery Use manual battery test switch on base of unit Connector Manual Battery to test. Red LED indicates normal operation. Test Switch Red LED (See Figure 8) Socket π 1 800 295-5510 uline.ca PAGE 2 OF 6 0624 IH-6508...
  • Page 3 H-6508 1 800 295-5510 uline.ca SEÑALAMIENTO "EXIT" CON CABLEADO HERRAMIENTAS NECESARIAS Desarmador de Desarmador de Cruz Cabeza Plana SEGURIDAD ¡PRECAUCIÓN! Cuando utilice equipos • El uso de accesorios no recomendados por eléctricos, siga siempre las precauciones el fabricante podría causar situaciones no básicas de seguridad, incluyendo lo siguiente:...
  • Page 4 Prueba de LED Rojo para hacer una prueba. El LED rojo indica un Batería Orificio funcionamiento normal. (Vea Diagrama 8) π 1 800 295-5510 uline.ca PAGE 4 OF 6 0624 IH-6508...
  • Page 5 H-6508 1 800 295-5510 uline.ca ENSEIGNE DE SORTIE CÂBLÉE – « EXIT » OUTILS REQUIS Tournevis à tête plate Tournevis cruciforme SÉCURITÉ MISE EN GARDE! Lors de l'utilisation d'un • N'utilisez pas cet équipement à d'autres fins appareil électrique, vous devez toujours que celles prévues.
  • Page 6 Utilisez l'interrupteur d'essai de batterie manuel sur batterie manuel Emboîture DEL rouge la base de l'unité pour vérifier son fonctionnement. Le voyant à DEL rouge indique que l'unité fonctionne normalement. (Voir Figure 8) 1 800 295-5510 uline.ca PAGE 6 OF 6 0624 IH-6508...