OPERATION AND SETTINGS
1. Low Temperature (LT) knob: This set point establishes the low temperature limit setting. Below this setpoint the fan will
turn off and the unit will be in sampling mode. This setting is adjustable from 30°F to 55°F (-1°C to 13°C), factory
preset: 40°F(4°C);
2. High Temperature (HT) knob: This set point establishes the high temperature limit setting. Above this set setpoint the
fan will turn off and the unit will be in sampling mode. This setting is adjustable from 65°F to 95°F (18°C to 35°C),
factory preset: 90°F(32°C);
3. Low Humidity (LH) knob: This set point establishes the low humidity limit setting Below this setpoint the fan will turn off
and the unit will be in sampling mode. This setting is adjustable from 10%-40% RH and OFF factory preset:30% RH; If
the Set point is OFF, low humidity monitoring is disabled;
4. High Humidity (HH) knob. This set point establishes the high humidity limit setting. Above This set setpoint the fan will
turn off and the unit will be in sampling mode. This setting is adjustable from 45%-80% RH and is factory preset:50%
RH.
Slide switch for CFM control(for FA100X):
OFF/50CFM/80CFM/100CFM constant CFM for each speed.
Factory preset for 80 CFM.
CLEANING & MAINTENANCE
!
Warning – RISK OF ELECTRIC SHOCK OR INJURY.
• Before servicing or cleaning the unit, make sure power is switched off at service panel.
• Be sure unit is not running before cleaning & maintenance. Blower wheels are sharp and can cause injury.
!
Caution:
NEVER IMMERSE ELECTRICAL PARTS OR OPTIONAL AIR FILTER IN WATER.
EXPLODED VIEW
PART
PART NAME
1
cover
2
insect filter
3
inlet duct collar
4
housing
5
outlet duct collar
6
hanger
control box-
7
control box-
8
fan assembly
QTY.
1
1
1
1
1
4
QUF100X
1
FA100X
1
Model:FA100X
4
CFM
OFF
50
80
100
1
2
3
4
5
6
7
8