YOUR SAFETY IS IMPORTANT TO US
This guide contains instructions regarding safety as well as precautions to take to ensure a compliant and successful
installation. Please pay special attention to this symbol and follow any instruction given.
Pre-assembled, self-regulating heating cables for pipes, roofs, gutters and downspouts
Congratulations, you are now a ProtecTHERM system owner! Please read
and save these instructions. Read carefully before attempting to assemble,
install, operate or maintain your ProtecTHERM
others by observing all safety information. Failure to comply with
instructions could result in personal injury and/or property damage! Retain
instructions for future reference.
Description
These heating cables provide pipe, roof, and gutter system protection from
damage due to freezing, snow and ice, and can be used in residential and
commercial applications. The self-regulated cables automatically adjust heat
output according to the ambient temperature conditions. Under cooler
conditions the heat output increases, and as the temperature rises the
output decreases to save energy. The cables operate on 120V or 240V and are
available in various pre-assembled lengths.
120V cable has an end seal,
cold lead and plug.
Features
• 120V cable includes a 30-inch cold lead and plug.
• 240V cable requires a power connection in an appropriate junction box.
• Suitable for plastic or metal pipes, shingle and metal roofs, gutters and
downspouts.
• Ease of installation, as the cable can be overlapped without the risk of
becoming overheated or burnt.
General Safety Information
Read all instructions in this manual and the following installation instructions
and safety warnings. Electrical cables, if not installed correctly or if damaged,
can present a fire or shock hazard or short out.
1. Depending on the length of the cable, a dedicated electrical circuit may
be required.
2. Installation must be in compliance with National Electrical Codes (NEC)
or Canadian Electrical Codes (CEC).
3. Use 30-mA ground fault protection on each heating cable branch circuit
for maximum protection.
4. Use only fire-resistant insulation, such as certified fiberglass or preformed
foam. Do not embed heating cable in the insulation.
120V plug-in – 240V hard-wired
system. Protect yourself and
TM
240V cable has an end seal and a cold
lead; requires a power connection in
an appropriate junction box.
5. Use fiberglass tape (PT-FGT, sold separately) or nylon cable ties when
attaching cable to metal pipes. Do not use wire or metal clamps. On
plastic pipes, attach the full length of cable with aluminum tape (PT-
ALUT, sold separately).
6. Before installing or servicing, ensure that all power to circuits is OFF.
7. Do not twist cable during installation; the cable's minimum bending
radius is 1.5 in.
8. Do not install heating cable under roofing material.
9. Do not expose cable to temperatures above 65 °C (150 °F), as this will
damage the cable.
10. Do not use extension cords.
11. Save all instructions for future reference.
WARNING: Do not use damaged heating cables, cold leads or
plugs. Remove and replace immediately.
Specifications
Length
Power Output on Pipe
Model
Voltage
(ft)
at 10 °C (50 °F)
CS061PR006 120V
6
CS061PR012 120V
12
CS061PR018 120V
18
CS061PR024 120V
24
CS061PR037 120V
37
CS061PR050 120V
50
CS061PR075 120V
75
CS061PR100 120V
100
CS061PR125 120V
125
CS062PR050 240V
50
CS062PR075 240V
75
CS062PR100 240V
100
CS062PR125 240V
125
CS062PR150 240V
150
Power Output in Ice &
Max. exposure
Snow at 0° C (32° F)
temperature
36 W
48 W
65 °C (150 °F)
72 W
96 W
65 °C (150 °F)
108 W
144 W
65 °C (150 °F)
144 W
192 W
65 °C (150 °F)
222 W
296 W
65 °C (150 °F)
300 W
400 W
65 °C (150 °F)
450 W
600 W
65 °C (150 °F)
600 W
800 W
65 °C (150 °F)
750 W
1000 W
65 °C (150 °F)
300 W
400 W
65 °C (150 °F)
450 W
600 W
65 °C (150 °F)
600 W
800 W
65 °C (150 °F)
750 W
1000 W
65 °C (150 °F)
900 W
1200 W
65 °C (150 °F)
ProtecTHERM Instructions Manual